Open Communication Via Industrial Ethernet - Siemens CPU 410-5H Process Automation System Manual

Simatic pcs 7 process control system
Table of Contents

Advertisement

Supplementary information
16.6 Communication services
Reference
For further information on the SNMP communication service and diagnostics with SNMP,
refer to the
16.6.8

Open Communication Via Industrial Ethernet

Functionality
The following services are available for open IE communication:
● Connection-oriented protocols:
Prior to data transmission connection-oriented protocols establish a logical connection to
the communication partner and close this again, if necessary, after transmission is
complete. Connection-oriented protocols are used when security is especially important
in data transmission. A physical cable can generally accommodate several logical
connections. The maximum job length is 32 Kbytes.
The following connection-oriented protocols are supported for the FBs for open IE
communication:
– TCP to RFC 793
– ISO on TCP according to RFC 1006
● Connectionless protocols:
Connectionless protocols operate without a logical connection. There is also no
establishing or terminating a connection to remote partner. Connectionless protocols
transfer the data unacknowledged and thus unsecured to the remote partner. The
maximum message frame length is 1472 bytes.
The following connectionless protocols are supported for the FBs for open
communication via Industrial Ethernet:
– UDP according to RFC 768
232
PROFINET System Description.
Note
ISOonTCP
For data communication with third-party systems via RFC1006, the connection partner
must adhere to the maximum TPDU size (TPDU = Transfer Protocol Data Unit)
negotiated in the ISOonTCP connection establishment.
The single-cast and broadcast modes are supported.
CPU 410-5H Process Automation/CPU 410 SMART
System Manual, 10/2013, A5E32631667-AA

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cpu 410 smartSimatic pcs 7

Table of Contents