Levelflex FMP50 PROFIBUS PA
Empty calibration
Navigation
Description
User entry
Factory setting
Additional information
Full calibration
Navigation
Description
User entry
Endress+Hauser
The Medium group parameter presets the Medium property parameter (→  134) as
follows:
Medium group
Others
Water based (DC >= 4)
The Medium property parameter can be changed at a later point of time. However,
when doing so, the Medium group parameter retains its value. Only the Medium
property parameter is relevant for the signal evaluation.
The measuring range may be reduced for small dielectric constants. For details refer
to the Technical Information (TI) of the respective device.
 Setup → Empty calibration
Distance process connection to min. level.
Depending on the probe
Depending on the probe
 31
Empty calibration (E) for level measurements in liquids
 Setup → Full calibration
Span: max. level - min level.
Depending on the probe
Medium property (→  134)
Unknown
DC 4 ... 7
E
0%
Operating menu
A0013178
123