Section 2: Starting The Installation; Installation Steps; Terminal Descriptions; Installation And Operation Of The Bus-D485 - Garnet PC-732G Manual

Table of Contents

Advertisement

IP-500G WiFi Communicator
The IP-500G Communicator has the same capabilities as the 3G-COM-G / 4G-MAX-G
communicator, but instead of a GSM connection, it will use a WIFI connection to
communicate. It connects to the panel via the BUS-C485. It can also be used in
three different ways:
• As the main communicator with or without back-up.
• As a back-up communicator for other media.
• As a simultaneous communicator alongside other media.
Please refer to the explanation of the different scenarios of
communication, backup scenario and dual or simultaneous reporting scenarios.
EXP-8Z Zone Expander
It is a wired 8-zone expander for the PC-732G® panel.
The system supports a maximum of 3 expanders, growing to a maximum of 32
zones.
Each expander must be addressed and assigned in the programming to the diffe-
rent zones of the system.
Connects to BUS-D485 and can be installed inside or outside the panel enclosure
PC-732G®.
Supervised Auxiliary Power Supply FRA-200
The FRA-200 power supply provides an extra power supply for systems where
power consumption is important. At the same time, it can have a battery backup
for AC outages.
The installer should distribute the power consumptions so that, in the event of an
AC power failure, both batteries are evenly discharged (the main battery of the
panel and the battery of the auxiliary source FRA-200).
The FRA-200 source is also connected to the BUS-D485 and is fully supervised by
the PC-732G® alarm panel. The panel will indicate low battery and mains failure of
the auxiliary source.
Access Control CP-4000
Each CP-4000 access control module can control up to two independent doors,
with entry and exit readers or a combined reader with a button and exit require-
ment.

SECTION 2: Starting the Installation

This section will provide a comprehensive description of how to install and
configure the different devices and zones.

2.1 Installation Steps

Read this section thoroughly before you begin. Once you have a general unders-
tanding of the installation process, work carefully through each step.
Step 1: Create a sketch
Draw a sketch of the construction, to get an idea about the location of detectors,
keypads and other modules that will be placed.
Step 2: Mount the Control Panel
Mount the control panel in a dry area near the entrance of a power outlet.
of non-interruptible AC power.
NOTE: All wiring must be completed before connecting the battery, or applying AC
to the control panel.
Step 3: Installing devices on the BUS-D485 (See also Section 2.3) Install the bus
to each of the modules following the guidelines provided in Section 2.3 of this
manual.
Step 4: Install the Zones (Section 2.8)
You must remove power from the PC-732G® panel to install zone circuits. Please
refer to Section 2.8 when wiring zones, using normally closed circuits, RFL end-of-
line resistors, fire zones and Keyswitch "Arming" zones.
Step 5: Complete Installation (Section 2.2)
Complete all other installations including sirens, programmable outputs if availa-
ble, and other devices following the guidelines provided in Section 2.2 (Terminal
Descriptions).
Step 6: Energising the Control Panel
Once the installation of all zones and keypads is complete, activate the Control Pa-
nel. First, connect the red battery cable to the positive terminal and the black cable
to the negative terminal. Then connect the AC power.
NOTE: Always connect the battery before connecting AC power. AC power must be
applied for at least 10 seconds, or the control panel will not operate.
The control panel will not activate with battery connection alone.
Step 7: Keyboard Assignment (Section 2.5)
In order for the keypads to be properly monitored, each one must be assigned
6
to a different "address" on the bus. Please follow the guidelines provided in Section
2.5.
Step 8: Monitoring (Section 2.6)
Supervision of each module must be enabled by programming. Verify that all mo-
dules are recognised by the system, according to the instructions in Section 2.6.
Step 9: Programming the System (Sections 4 and 5)
Section 4 explains how to program the control. Section 5 contains a complete des-
cription of several of the programmable features, which options are available and
how they work. Complete the programming sheets before attempting to program
the system.
Step 10: Test the System
Fully test the system to ensure that all features and functions are operating as
programmed.

2.2 Terminal Descriptions

Battery Connection: +BAT-
A 12V, 4/7Ah rechargeable battery is used as a backup power source in the event
of an AC failure. The battery also provides additional power when the demand on
the control panel exceeds the power capacity of the transceiver, such as when the
system is in alarm.
NOTE: Do not connect the battery until all other installations are complete. Con-
nect the battery before connecting the AC.
Connect the RED battery cable to the positive battery terminal; connect the BLACK
cable to the negative.
Transformer terminals: ~AC~
The control panel requires a 16.5 volt, 25 VA transformer. Connect the transformer
primary to an interruptible outlet and the secondary to these terminals.
NOTE: Be sure to clearly identify the transformer primary and secondary wires
before connecting. Do not connect the transformer until all other installations have
been completed.
Auxiliary power terminals: - AUX+
These terminals provide up to 700mA of auxiliary current at 12 VDC for devices re-
quiring power. Connect the positive side of any device requiring power to the +AUX
terminal, the negative side to -AUX. The AUX output is protected. This means that if
too much current flows through these terminals (such as in a short circuit), the PC-
732G® panel will temporarily shut down the output until the problem is corrected.
Siren Output Terminals: +BELL-
These terminals provide up to 1.4A of DC current at 12VDC to power bells, sirens,
strobes or other warning equipment. Connect the positive of any warning device to
+BELL, the negative to -BELL.
Note that the Siren output is protected: if there is a high consumption of these
terminals (such as in a short circuit), the protection will open. Three am- peres can
be consumed for short periods only.
The Bell output is supervised. If no warning device is used, connect a 1000 ohms
resistor between the +BELL - terminals to prevent the panel from displaying a fault
condition. For more information (see section 3.5 "Commands [*]).
BUS-C485 terminals: +AUX-, A, B.
The Accessory bus is used by the control panel to communicate with the 3G-COM-G
/ 4G-MAX-G and IP-500G communicators. Each Communicator has four bus termi-
nals which must be connected to the four terminals of
this bus on the control panel.
Programmable Output Terminals: PGM1 to PGM2
Each PGM output is designed so that when activated by the control panel, the ter-
minal connects to ground. PGM1-PGM2 can draw up to 50mA of current. Connect
the positive of an LED or buzzer to the +AUX terminal and the negative to the PGM.
If more than 50mA of current is required, a relay must be used.
Please study the PGM wiring in the diagram. For a list of programmable output
options, please see section 5.9 "PGM Output Options".
Zone Input Terminals - Z1 to Z6
Each detection device should preferably be connected to one zone in the control
panel. However, it is possible to install multiple devices on the same zone. For zone
installation specifications, please see section 2.8 "Zone Wiring".

2.3 Installation and Operation of the BUS-D485

The data bus is used by the PC-732G® panel to communicate with all connected
modules and vice versa. Terminals (A) and (B) are for data.
NOTE: The four bus terminals on the PC-732G® panel must be connected to the
four bus terminals or bus cables on all modules.

Advertisement

Table of Contents
loading

Table of Contents