Frequency setting by analog input (terminal 2, 4)
(4) Frequency setting signal (current) bias/gain adjustment method
(a) Method to adjust any point by application of a voltage (current) to across terminals 2-5 (4-5).
Operation
1.
Confirm the RUN indication and operation
mode indication
The inverter should be at a stop.
The inverter should be in the PU operation
mode.
(Using
)
2.
Press
to choose the parameter setting
mode.
3.
Turn
until
4.
Press
until
5.
Turn
until
Set to C4 Terminal 2 frequency setting gain.
6.
Press
to display the analog voltage
(current) value (%).
7.
Apply a 5V (20mA) voltage (current).
(Turn the external potentiometer connected
across terminals 2-5 (across terminals 4-5) to
maximum (any position).)
NOTE
After performing operation in step 6, do not touch
8.
Press
to set.
Turn
Press
Press
REMARKS
If the frequency meter (display meter) connected across the terminals FM-SD does not indicate exactly 60Hz, set the
calibration parameter C0 FM terminal calibration. (Refer to page 155)
If the gain and bias of frequency setting voltage (current) are too close, an error (
176
appears.
appears.
(
) appears.
to read another parameter.
to return to the
indication (step 4).
twice to show the next parameter (
Display
PRM indication is lit.
(The
parameter
number
appears.)
C0 to C25 setting
is enabled.
Terminal 2 input is
Terminal 4 input is
selected
selected
Analog voltage (current)
value (%) across terminals 2-
5 (across terminals 4-5)
* The value is nearly 100 (%) in the maximum position of
the potentiometer.
until completion of calibration.
Terminal 2 input is
selected
Flicker...Parameter setting complete!!
* The value is nearly 100 (%) in the maximum position of
the potentiometer.
).
read
previously
Terminal 4 input is
selected
) may be displayed at setting.