Mounting The Panels On The Wall - WEG AFW900 User Manual

Cabinet built variable speed drives
Table of Contents

Advertisement

Available languages

Available languages

Installing

4.2 MOUNTING THE PANELS ON THE WALL

The panels must be installed in the electric room according to the layout below. The strength of the wall, wall plugs
and screws must be suitable for the weight of the equipment.
1
For panels with a mass of up to 100 kg and a depth of less than or equal to 300 mm, the materials below must
be used:
Ciser universal wall plug Ø10x50 mm.
A
Pull-out resistance: Concrete base: 94 kgf.
Hollow base: 17 kgf.
Slotted/Phillips truss head screw 6x60 mm.
The details for fastening to concrete and hollow bricks can be seen in
B
C
Figure 4.3: Details of the fastening of the panels to concrete and hollow brick walls
D
24 | AFW900
Figure 4.2: Fixing details of AFW Frames C, D and E
2
50
CONCRETO
3
Figure 4.3 on page
24.
TIJOLO OCO
4
5

Advertisement

Table of Contents