Power Cable Minimum Gauge Table - WEG AFW900 User Manual

Cabinet built variable speed drives
Table of Contents

Advertisement

Available languages

Available languages

Installing

4.4.2 Power Cable Minimum Gauge Table

The following table was prepared considering a maximum ambient temperature of 40 °C, a cable with PVC jacket
(without identification) and/or Silicone (SIL) jacket.
NOTE!
For the correct cable sizing, take into account the installation conditions, the maximum permissible
line voltage drop, and follow the electrical instructions defined by local regulations.
30 | AFW900
Table 4.2: Minimum gauge definitions
Supply Voltage (V)
Rated Current (A)
200-240
380-480
Minimum Gauges
Recommended (mm²)
R/S/T
U/V/W
4.6
2.5
6
2.5
7.5
2.5
10.6
2.5
13
4.0
19
4.0
26
6.0
34
10
45
16
56
25
70
25
80
35
110
50
135
70
150
35 SIL
172
35 SIL
195
50 SIL
250
70 SIL
2.8
2.5
3.6
2.5
4.8
2.5
6.5
2.5
9.6
2.5
14
4.0
17
4.0
26
6.0
33
10
39
10
50
16
62
16
74
16
96
16 SIL
124
25 SIL
146
35 SIL
172
50 SIL
203
70 SIL
242
95 SIL
PE
16
16
16
35
35
35
35
25
35
10
16
25
25
35
50

Advertisement