This message is for the use case when an implementation has detected that a Power Supply input is lost
or out of range.
Severity: Info
Serviceable: No
Automatically notify Support: No
Alert Category: System - Other
SNMP Trap ID:
CIM Prefix: PLAT CIM ID: 0096
User Action:
Complete the following steps:
1. If the server has recently been installed, moved, serviced, or upgraded, verify that the DIMM is
properly seated and visually verify that there is no foreign material in any DIMM connector on that
memory channel. If either of these conditions is found, correct and retry with the same DIMM. (Note:
The event Log might contain a recent FQXSFMA0011I event denoting detected change in DIMM
population that could be related to this problem.)
2. If no problem is observed on the DIMM connectors or the problem persists, replace the DIMM
identified by LightPath and/or event log entry.
3. If problem recurs on the same DIMM connector, replace the other DIMMs on the same memory
channel.
4. Check Lenovo support site for an applicable service bulletin or firmware update that applies to this
memory error.
5. If problem recurs on the same DIMM connector, inspect connector for damage. If damage found or
problem persists, collect Service Data log.
6. Contact Lenovo Support.
• FQXSPPW0005I: [PowerSupplyElementName] is operating in an Input State that is out of range.
This message is for the use case when an implementation has detected a Power Supply that has input out
of range.
Severity: Info
Serviceable: No
Automatically notify Support: No
Alert Category: System - Other
SNMP Trap ID:
CIM Prefix: PLAT CIM ID: 0098
User Action:
Information only; no action is required.
• FQXSPPW0006I: [PowerSupplyElementName] has lost input.
This message is for the use case when an implementation has detected a Power Supply that has input
that has been lost.
Severity: Warning
Serviceable: No
Automatically notify Support: No
Alert Category: Warning - Power
SNMP Trap ID:
CIM Prefix: PLAT CIM ID: 0100
User Action:
98
ThinkSystem ST650 V3 Messages and Codes Reference