Schneider Electric. National Electrical Code and NEC are registered trademarks of National Fire Protection Association, Inc. All other trademarks are property of their respective companies. ECopyright 2008-2010 Eaton Corporation, Raleigh, NC, USA. All rights reserved. No part of this document may be reproduced in any way without the express written approval of Eaton Corporation.
Engineer, or the warranty terms specified on page W-1 become void. This service is offered as part of the sales contract for the UPS. Contact an Eaton service representative in advance (usually a two-week notice is required) to reserve a preferred startup date.
Page 10
INTRODUCTION Figure 1‐1. Power Xpert 9395 550/275 UPS Cabinet EATON Power Xpert 164201716 Rev 3 www.eaton.com/powerquality 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
Page 11
INTRODUCTION Figure 1‐2. Power Xpert 9395 550/275 UPS Cabinet with the Field Installed UPM 164201716 Rev 3 www.eaton.com/powerquality Power Xpert 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
® shipped with the UPS. See Chapter 8, “Communication,” for additional information. Options and Accessories Contact an Eaton sales representative for information about the following options. 1.2.1 Integrated Battery Cabinets Battery backup protection can be provided by equipping the UPS system with up to four Power Xpert 9395 battery cabinets containing sealed lead‐acid, maintenance‐free...
1.2.6 Separate Rectifier Input If a FI-UPM is to be installed with the Power Xpert 9395 550/275 UPS at the initial installation or in the future, the UPS can be supplied with separate rectifier inputs for each UPM. Separate inputs provide increased flexibility and reliability by allowing multiple input sources to supply the UPS.
Inherent Redundancy To deliver greater reliability, the Power Xpert 9395 UPS can be configured by an authorized Eaton Customer Service Engineer for inherent redundancy if a FI-UPM is installed. When configured, the UPS automatically becomes redundant if the load is at or below the capacity of the UPMs minus the capacity of one UPM.
UPMs in distributed bypass and parallel systems must use a separate battery system. A supplemental 48 Vdc shunt trip signal for the battery disconnect device is provided by the UPS, but is not required for normal operation. 164201716 Rev 3 www.eaton.com/powerquality Power Xpert 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
At a minimum, Chapters 1 through 4 and Chapter 7 should be examined. Read through each procedure before beginning the procedure. Perform only those procedures that apply to the UPS system being installed or operated. EATON Power Xpert 164201716 Rev 3 www.eaton.com/powerquality 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
This symbol indicates that you should not discard waste electrical or electronic equipment (WEEE) in the trash. For proper disposal, contact your local recycling/reuse or hazardous waste center. 164201716 Rev 3 www.eaton.com/powerquality Power Xpert 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
Detailed illustrations of the cabinet, including dimension and connection point drawings. Refer to the Eaton 9315, 9390 and 9395 Sync Control Installation and Operation Manual for the following additional information: Installation instructions, including site preparation, planning for installation, and wiring and safety information.
Keep the UPS door and front panels closed to ensure proper cooling airflow and to protect personnel from dangerous voltages inside the unit. Do not install or operate the UPS system close to gas or electric heat sources. 164201716 Rev 3 www.eaton.com/powerquality Power Xpert 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
Page 20
Une mise au rebut réglementaire des batteries est obligatoire. Consulter les règlements en vigueur dans votre localité. Ne jamais jeter les batteries au feu. L'exposition aux flammes risque de les faire exploser. EATON Power Xpert 164201716 Rev 3 www.eaton.com/powerquality 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
Page 21
Section I Installation 164201716 Rev 3 www.eaton.com/powerquality Power Xpert 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
Page 22
EATON Power Xpert 164201716 Rev 3 www.eaton.com/powerquality 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
Engineer, or the warranty terms specified on page W-1 become void. This service is offered as part of the sales contract for the UPS. Contact an Eaton service representative in advance (usually a two-week notice is required) to reserve a preferred startup date.
Page 24
95%, noncondensing C A U T I O N If Eaton battery cabinets are located in the same room as the UPS, the battery cabinet environmental requirements supercede the UPS requirements. Operating temperatures above the recommended range will result in decreased battery life and performance, and will reduce or void the battery warranty. Refer to Eaton's Terms and Conditions of Sale with Battery Replacement Coverage and the Battery Replacement Price Book for more information.
CANNOT be used. DO NOT bond the inverter center point (E12) to ground: this is an internal UPS function and requires no additional work by the installer or user. Please contact the Eaton help desk listed in Chapter 1 for additional guidance regarding dual high impedance ground sources.
Page 30
Because of the future upgradability to a fully rated 550 kVA UPS with the addition of the FI-UPM, the UPS wiring is specified for 550 kVA in Table 3‐4 through Table 3‐7. EATON Power Xpert 164201716 Rev 3 www.eaton.com/powerquality 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
Page 31
Figure 6‐5 on page 6-8 or Figure 6‐6 on page 6-9. NOTE Because of the future upgradability to a fully rated 550 kVA UPS with the addition of the FI-UPM, the UPS wiring is specified for 550 kVA. 164201716 Rev 3 www.eaton.com/powerquality Power Xpert...
Page 32
NOTE Because of the future upgradability to a fully rated 550 kVA UPS with the addition of the FI-UPM, the UPS wiring is specified for 550 kVA. 3-10 EATON Power Xpert 164201716 Rev 3 www.eaton.com/powerquality 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
Page 33
NOTE Because of the future upgradability to a fully rated 550 kVA UPS with the addition of the FI-UPM, the UPS wiring is specified for 550 kVA. 3-11 164201716 Rev 3 www.eaton.com/powerquality Power Xpert 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
Page 34
NOTE Because of the future upgradability to a fully rated 550 kVA UPS with the addition of the FI-UPM, the UPS wiring is specified for 550 kVA. 3-12 EATON Power Xpert 164201716 Rev 3 www.eaton.com/powerquality 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
Page 35
Table 3‐9. Neutral Bonding Jumper Wire Size (Four Wire Only - All Ratings) Neutral Bonding Jumper (Four Wire Output Only) Minimum Conductor Size AWG or kcmil Number (each) 3-13 164201716 Rev 3 www.eaton.com/powerquality Power Xpert 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
Page 36
90°C. See Table 3‐10 for external power cable terminations, Table 3‐11 for supplied external wiring terminal hardware, and Table 3‐12 for recommended installation parts and tools not supplied by Eaton Corporation. For a UPS with separate rectifier input terminals for the UPMs, E1 through E3 are pressure terminations, UL and CSA rated at 90°C.
Page 37
Rectifier Input, Bypass Input, Conical Washer 180500037-120 Battery Input, and Output Rectifier Input, Bypass Input, 180200001-07 Battery Input, and Output Table 3‐12. Recommended Installation Parts and Tools (Not Supplied by Eaton Part Size Quantity Manufacturer Part Number Notes 2/0 AWG Thomas &...
Page 38
NOTE 2 Because of the future upgradability to a fully rated 550 kVA UPS with the addition of the FI-UPM, these conduit sizes are specified for 550 kVA. 3-16 EATON Power Xpert 164201716 Rev 3 www.eaton.com/powerquality 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
Page 39
NOTE Because of the future upgradability to a fully rated 550 kVA UPS with the addition of the FI-UPM, these breaker sizes are specified for 550 kVA. 3-17 164201716 Rev 3 www.eaton.com/powerquality Power Xpert 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
Page 40
The battery wiring used between the battery and the UPS should not allow a voltage drop of more than 1% of nominal DC voltage at rated battery current. 3-18 EATON Power Xpert 164201716 Rev 3 www.eaton.com/powerquality 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
Alarm relay contacts have a maximum current rating of 5A and a switched voltage rating of 30 Vac and 28 Vdc. Alarm relay wiring should be a minimum of 22 AWG. 3-19 164201716 Rev 3 www.eaton.com/powerquality Power Xpert 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
CANNOT be used. DO NOT bond the inverter center point (E12) to ground: this is an internal UPS function and requires no additional work by the installer or user. Please contact the Eaton help desk listed in Chapter 1 for additional guidance regarding dual high impedance ground sources.
Carefully inspect the outer packaging for evidence of damage during transit. C A U T I O N Do not install a damaged cabinet. Report any damage to the carrier and contact an Eaton service representative immediately. NOTE For the following step, verify that the forklift or pallet jack is rated to handle the weight of the cabinet (see Table 3‐1 on page 3-2 for cabinet weight).
Page 44
Inspect the contents for any evidence of physical damage, and compare each item with the Bill of Lading. If damage has occurred or shortages are evident, contact an Eaton service representative immediately to determine the extent of the damage and its impact on further installation.
Page 45
UPS INSTALLATION PLAN AND UNPACKING Figure 3‐8. Power Xpert 9395 550/275 UPS Cabinet as Shipped on Pallet 3-23 164201716 Rev 3 www.eaton.com/powerquality Power Xpert 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
End forklift slots may be used for minor positioning if the forks are kept in a horizontal position with no upward angling. If these instructions are not followed, damage to the wiring channel and wiring will occur. 164201716 Rev 3 www.eaton.com/powerquality Power Xpert 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
Page 48
Step 13. 13. If installing a tie cabinet or distribution panel for a distributed bypass system, proceed to paragraph 4.5; otherwise, proceed to paragraph 4.6. EATON Power Xpert 164201716 Rev 3 www.eaton.com/powerquality 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
UPS SYSTEM INSTALLATION UPM Removable Front Panel Shipping Bracket Bolts Pallet Shipping Bracket Left Side Shipping Bolts Bracket Figure 4‐1. Removing the Left Side Shipping Bracket 164201716 Rev 3 www.eaton.com/powerquality Power Xpert 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
Front Door Removable Left Front Panel Shipping Bracket Bolts Pallet Right Side Shipping Bracket Shipping Bracket Bolts Figure 4‐2. Removing the Right Side Shipping Bracket EATON Power Xpert 164201716 Rev 3 www.eaton.com/powerquality 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
4.5. Battery System Installation If installing an Eaton battery cabinet, refer to the Power Xpert 9395 Integrated Battery Cabinet (Model IBC-L) Installation Manual, listed in paragraph 1.8 on page 1-10. If installing a customer-supplied battery system, install the battery system according to the battery and battery system manufacturer's instructions and all applicable codes and regulations, including the NEC, Article 480.
Remove the screws securing the internal safety shield panel and remove the panel to gain access to the input, output, and battery terminals. Retain the hardware for later use. EATON Power Xpert 164201716 Rev 3 www.eaton.com/powerquality 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
Page 53
UPS cabinet. See paragraph 3.2.2 on page 3-7 for wiring and termination requirements. 164201716 Rev 3 www.eaton.com/powerquality Power Xpert 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
Page 54
See paragraph 3.2.2 on page 3-7 for wiring and termination requirements. 15. Proceed to paragraph 4.6.3. EATON Power Xpert 164201716 Rev 3 www.eaton.com/powerquality 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
Bottom Entry Conduit Landing for AC Input and Output, and DC Input BOTTOM VIEW (Remove panel to drill or punch conduit holes.) Figure 4‐4. Conduit and Wire Entry Locations 164201716 Rev 3 www.eaton.com/powerquality Power Xpert 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
AC Input to UPS Bypass (A, B, C) (See Figure 4‐7 for Detail AA.) ISBM UPM 1 Figure 4‐6. UPS Power Terminal Locations – Common Rectifier Feed 4-11 164201716 Rev 3 www.eaton.com/powerquality Power Xpert 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
AC Input to UPS Bypass (A, B, C) (See Figure 4‐9 for detail AA.) ISBM UPM 1 Figure 4‐8. UPS Power Terminal Locations – Separate Rectifier Feed 4-13 164201716 Rev 3 www.eaton.com/powerquality Power Xpert 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
To install wiring to connections: NOTE An installed FI-UPM is always designated as UPM 4. If using an Eaton battery cabinet, proceed to Step 2; otherwise, proceed to Step 4. Route and connect the battery cables between the UPS and battery cabinet or...
UPS SYSTEM INSTALLATION DC Input from Battery + (E4) DC Input from Battery – (E5) Figure 4‐11. UPS Power Terminal Detail BB – Common Battery 4-16 EATON Power Xpert 164201716 Rev 3 www.eaton.com/powerquality 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
Chapter 7, “UPS Operating Instructions,” for shutdown instructions. Unfasten the front door latch and swing the door open (see Figure 4‐2 on page 4-4). 4-17 164201716 Rev 3 www.eaton.com/powerquality Power Xpert 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
Page 64
16. If removed, reinstall the safety shield panel removed in Step 6. Secure with the retained hardware. 17. If removed, reinstall the left front panel removed in Step 5 and secure with the retained hardware. 4-18 EATON Power Xpert 164201716 Rev 3 www.eaton.com/powerquality 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
(See Figure 4‐14 for detail.) (See Figure 4‐19 on page 4-25 for detail.) (See Figure 4‐16 on page 4-22 for terminal assignments.) Figure 4‐13. Interface Terminal Locations 4-19 164201716 Rev 3 www.eaton.com/powerquality Power Xpert 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
Page 66
Building Alarm 5 Return NOTE “Return“ indicates connection to electronics circuit ground. “Common” indicates connection to common side of isolated relay contact. 4-20 EATON Power Xpert 164201716 Rev 3 www.eaton.com/powerquality 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
NOTE Do not directly connect relay contacts to the mains related circuits. Reinforced insulation to the mains is required. NOTE Alarm relay wiring should be a minimum of 22 AWG Figure 4‐15. Typical Alarm Relay Connection 4-21 164201716 Rev 3 www.eaton.com/powerquality Power Xpert 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
NOTE A jumper wire must be connected between pins 1 and 2 on TB1, if the normally-closed REPO contact is not used. Figure 4‐16. Terminal Blocks TB1, TB2, and TB3 Connector Assignments 4-22 EATON Power Xpert 164201716 Rev 3 www.eaton.com/powerquality 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
(see Figure 4‐4 on page 4-9). 10. Reinstall the interface entry plates and install the conduit. 11. If using a Eaton battery cabinet, proceed to Step 12; otherwise, proceed to Step 15. 12. Route the Shunt trip and Aux wiring from the battery cabinet or battery disconnect to the UPS cabinet.
NOTE Battery aux and DC shunt trip wiring should be a minimum of 18 AWG. Figure 4‐18. Typical Battery Interface Connection – Separate Battery System 4-24 EATON Power Xpert 164201716 Rev 3 www.eaton.com/powerquality 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
NOTE When installing external wiring to X-Slot cards, conduit must be installed to the UPS cabinet. When installing internal wiring to X-Slot terminals, route the wiring through the internal opening in the X-Slot communication bay. For installation and setup of an X-Slot card, contact an Eaton service representative (see page 1-10). To install wiring to connections: If not already installed, install the LAN and telephone drops.
NOTE The REPO switch must be a normally-open or normally-closed latching‐type switch not tied into any other circuits. NOTE This procedure is intended to be used for the installation of the Eaton-supplied REPO switch. If installing another manufacturer's switch, use this procedure only as a guide.
Page 73
Terminal Board TB1 in (Either Block) UPS Cabinet 3 NO TB1‐3 Twisted Wires (2) 7 lb in 14–22 AWG (0.8 Nm) 4 NO TB1‐4 (0.75–4.0 mm 4-27 164201716 Rev 3 www.eaton.com/powerquality Power Xpert 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
Figure 4‐22 shows the wiring connections if the normally-closed REPO contacts are used, and Figure 4‐23 shows alternative methods of connecting a REPO switch if using another manufacturer's switch. 4-28 EATON Power Xpert 164201716 Rev 3 www.eaton.com/powerquality 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
NOTE REPO normally-open and normally-closed return terminals are separated on the terminal board but are electrically in common. Figure 4‐23. Normally‐Closed and Normally‐Open REPO Switch Wiring 4-29 164201716 Rev 3 www.eaton.com/powerquality Power Xpert 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
Service Engineer, or the warranty terms specified on page W-1 become void. This service is offered as part of the sales contract for the UPS. Contact an Eaton service representative in advance (usually a two-week notice is required) to reserve a preferred startup date.
Page 77
- Accessories are mounted in installed locations and wiring is terminated inside the UPS cabinet. (OPTIONAL) - The debris shield covering the UPS cabinet ventilation grill is removed. - Startup and operational checks are performed by an authorized Eaton Customer Service Engineer. 4-31 164201716 Rev 3 www.eaton.com/powerquality...
Page 78
- Pull-chain wiring between the UPS cabinets is properly installed. - Adequate workspace exists around the UPS cabinets, the tie cabinet, and other cabinets. - Startup and operational checks are performed by an authorized Eaton Customer Service Engineer. 4-32 EATON Power Xpert 164201716 Rev 3 www.eaton.com/powerquality...
UPS. See Figure 4‐13 on page 4-19 and Figure 4‐19 on page 4-25 for X-Slot communication bay locations. 164201716 Rev 3 www.eaton.com/powerquality Power Xpert 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
Page 82
SCM II (see paragraph 5.5) To locate the appropriate terminals on the Powerware Hot Sync CAN Bridge Card, see Figure 5‐2 and Table 5‐1. EATON Power Xpert 164201716 Rev 3 www.eaton.com/powerquality 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
Normally‐open contact closes when UPS is on bypass. RMP II, RIM II, and SCM II connections. CAN L Can H CAN Input for parallel operation. Shield 164201716 Rev 3 www.eaton.com/powerquality Power Xpert 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
NOTE Setup of the Powerware Hot Sync CAN Bridge Card for parallel operation must be performed by an authorized Eaton Customer Service Engineer. Contact an Eaton service representative to schedule a date. 12. Reinstall the small top internal safety shield panel and secure with the cabinet mounted screws.
NOTE Use twisted-pair wiring between the UPS and MOB AUX contacts. NOTE Always confirm contact operation prior to wiring. Figure 5‐6. Distributed Bypass Pull-Chain Wiring with MOBs 164201716 Rev 3 www.eaton.com/powerquality Power Xpert 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
Page 88
MOB 2 Aux 2 Com MOB 3 Aux 2 Com Pull Chain MOB Common MOB 3 Aux 2 Com MOB 4 Aux 2 Com EATON Power Xpert 164201716 Rev 3 www.eaton.com/powerquality 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
11. If removed, reinstall the left front panel removed in paragraph 5.1, Step 4 and secure with the retained hardware. 12. Restart the UPS. See Chapter 7, “UPS Operating Instructions,” for startup instructions. 164201716 Rev 3 www.eaton.com/powerquality Power Xpert 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
INSTALLING OPTIONS AND ACCESSORIES NOTE Setup of the Powerware Hot Sync CAN Bridge Card must be performed by an authorized Eaton Customer Service Engineer. Contact an Eaton service representative to schedule a date. 13. To check the operation of the RMP II, ensure that the UPS is supplying the load via inverter or bypass.
12. Restart the UPS. See Chapter 7, “UPS Operating Instructions,” for startup instructions. NOTE Setup of the Powerware Hot Sync CAN Bridge Card must be performed by an authorized Eaton Customer Service Engineer. Contact an Eaton service representative to schedule a date.
INSTALLING OPTIONS AND ACCESSORIES NOTE Setup of the Powerware Hot Sync CAN Bridge Card must be performed by an authorized Eaton Customer Service Engineer. Contact an Eaton service representative to schedule a date. Install wiring between the SCM II terminal block TB2 and the monitoring equipment.
Surface Mount using #10 Pan Head Screws for Hanging. (Mount with vent holes facing up.) Dimensions are in millimeters [inches]. Figure 5‐12. Remote Monitor Panel II Dimensions 5-15 164201716 Rev 3 www.eaton.com/powerquality Power Xpert 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
Surface Mount using #10 Pan Head Screws for Hanging. (Mount with vent holes facing up.) Dimensions are in millimeters [inches]. Figure 5‐13. Relay Interface Module II Dimensions 5-16 EATON Power Xpert 164201716 Rev 3 www.eaton.com/powerquality 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
Surface Mount using #10 Pan Head Screws for Hanging. (Mount with vent holes facing up.) Dimensions are in millimeters [inches]. Figure 5‐14. Supervisory Contact Module II Dimensions 5-17 164201716 Rev 3 www.eaton.com/powerquality Power Xpert 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
Page 98
INSTALLING OPTIONS AND ACCESSORIES This page intentionally left blank. 5-18 EATON Power Xpert 164201716 Rev 3 www.eaton.com/powerquality 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
For manual transfers to bypass, the static switch is also used. The static switch is armed and ready during both types of transfers. 164201716 Rev 3 www.eaton.com/powerquality Power Xpert 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
DC voltage charge current to the battery. The battery is always connected to the UPS and ready to support the inverter should the utility input become unavailable. EATON Power Xpert 164201716 Rev 3 www.eaton.com/powerquality 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
UPS actively monitors the critical bus for power disturbances. When in this mode, the input and output contactors are closed and the link is maintained through the diode bridge. 164201716 Rev 3 www.eaton.com/powerquality Power Xpert 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
C A U T I O N The critical load is not protected from voltage or frequency fluctuations or power outages while the UPS is in Bypass mode. EATON Power Xpert 164201716 Rev 3 www.eaton.com/powerquality 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
(up to three times within a ten minute period). The fourth transfer locks the critical load to the bypass source and requires operator intervention to transfer. 164201716 Rev 3 www.eaton.com/powerquality Power Xpert 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
NOTE If the load requires a neutral, a bypass source neutral must be provided. DO NOT install both a source neutral and a bonding jumper. Figure 6‐5. UPS System – Common Rectifier Feed, Dual‐Feed Configuration EATON Power Xpert 164201716 Rev 3 www.eaton.com/powerquality 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
NOTE If the load requires a neutral, a bypass source neutral must be provided. DO NOT install both a source neutral and a bonding jumper. Figure 6‐6. UPS System with Field Installed UPM – Common Rectifier Feed, Common Battery, Dual‐Feed Configuration 164201716 Rev 3 www.eaton.com/powerquality Power Xpert...
NOTE If the load requires a neutral, a bypass source neutral must be provided. DO NOT install both a source neutral and a bonding jumper. Figure 6‐7. UPS System with Field Installed UPM – Common Rectifier Feed, Separate Battery, Dual‐Feed Configuration 6-10 EATON Power Xpert 164201716 Rev 3 www.eaton.com/powerquality 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
NOTE If the load requires a neutral, a bypass source neutral must be provided. DO NOT install both a source neutral and a bonding jumper. Figure 6‐8. UPS System with Field Installed UPM – Separate Rectifier Feed, Separate Battery, Dual‐Feed Configuration 6-11 164201716 Rev 3 www.eaton.com/powerquality Power Xpert 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
(BIB) is installed in the maintenance bypass and a single-feed UPS is being installed, a single feed to the maintenance bypass is acceptable for supplying both the UPS and the bypass. Figure 6‐9. Simplified Dual-Feed UPS with Maintenance Bypass Panel 6-12 EATON Power Xpert 164201716 Rev 3 www.eaton.com/powerquality 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
UPS will require at least one UPM to be in double-conversion mode at all times; otherwise, VMMS mode operates the same as it does in a single UPS system (see paragraph 6.2.4). 6-13 164201716 Rev 3 www.eaton.com/powerquality Power Xpert 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
Bypass mode. The distributed bypass system automatically returns to Online mode when the overload condition is cleared and system operation is restored within specified limits. 6-14 EATON Power Xpert 164201716 Rev 3 www.eaton.com/powerquality 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
If more modules than can support the load must be taken offline, the load must be transferred to maintenance bypass or shut down. 6-15 164201716 Rev 3 www.eaton.com/powerquality Power Xpert 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
In the Parallel Capacity (N+0) arrangement, if one UPS trips offline and goes to bypass, the remaining UPSs also go to bypass. 6-16 EATON Power Xpert 164201716 Rev 3 www.eaton.com/powerquality 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
Breakers Closed Output to Main Power Flow Critical Load Open Figure 6‐12. Path of Current through the UPSs in Battery Mode – Distributed Bypass 6-17 164201716 Rev 3 www.eaton.com/powerquality Power Xpert 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
NOTE If the load requires a neutral, a bypass source neutral must be provided. DO NOT install both a source neutral and a bonding jumper. Figure 6‐13. Typical Distributed Bypass System (1+1 and 2+0 Configurations) 6-19 164201716 Rev 3 www.eaton.com/powerquality Power Xpert 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
NOTE If the load requires a neutral, a bypass source neutral must be provided. DO NOT install both a source neutral and a bonding jumper. Figure 6‐14. Typical Distributed Bypass System (2+1 and 3+0 Configurations) 6-20 EATON Power Xpert 164201716 Rev 3 www.eaton.com/powerquality 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
NOTE If the load requires a neutral, a bypass source neutral must be provided. DO NOT install both a source neutral and a bonding jumper. Figure 6‐15. Typical Distributed Bypass System (3+1 and 4+0 Configurations) 6-21 164201716 Rev 3 www.eaton.com/powerquality Power Xpert 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
Page 122
UNDERSTANDING UPS OPERATION This page intentionally left blank. 6-22 EATON Power Xpert 164201716 Rev 3 www.eaton.com/powerquality 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
UPS operation. Figure 7‐1 shows the controls and indicators. Control Panel AC Input Breaker CB1 (Optional) (Not available with separate rectifier feed option.) ISBM UPM 1 Figure 7‐1. UPS Controls and Indicators 164201716 Rev 3 www.eaton.com/powerquality Power Xpert 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
The following paragraphs describe using the UPS control panel to monitor the UPS. See paragraph 7.3 for use of the operational controls. When the unit powers up, the screen displays the Eaton logo as shown in Figure 7‐2. To advance to the Main Menu and Mimic screen, press any control panel pushbutton once.
LCD in the UPS status area. This message is also written to the Active Events Log and may be added to the History Log. The messages are divided into four categories: alarms, notices, status, and commands. 164201716 Rev 3 www.eaton.com/powerquality Power Xpert 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
LOAD OFF Figure 7‐3. Parts of the LCD The UPS status area automatically scrolls between the Eaton model number, current date and time, active alarms, active notices, and load percent and battery runtime for the UPS. If the Environmental Monitoring Probe is installed, the temperature and humidity sensed by the probe will also be displayed.
The Battery screen displays the battery voltage (Vdc), the battery current (Idc), the minutes of Battery – UPM battery time remaining, and battery temperature. Battery temperature must be set up by an authorized Eaton Customer Service Engineer. When battery life decreases to less than 20%, Check Battery is displayed. Statistics The Statistics screen displays the hours on line and the total kW hours used.
Page 129
VMMS UPM Redundancy screen. Use the up or down arrow pushbutton to set the number of UPMs. Press SAVE or ABORT. Once the action is completed, the Module Management System Setup screen is displayed. 164201716 Rev 3 www.eaton.com/powerquality Power Xpert 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
Page 130
COM port to be set up, then press the SELECT pushbutton To return to the System Setup screen, press the ESC pushbutton EATON Power Xpert 164201716 Rev 3 www.eaton.com/powerquality 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
7.3.24 on page 7-27 or paragraph 7.4.27 on page 7-48. HOLD LOAD OFF BUTTON FOR 3 SECONDS TO TURN OFF LOAD CANCEL LOAD OFF Figure 7‐5. Load Off Screen 164201716 Rev 3 www.eaton.com/powerquality Power Xpert 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
Charger Off Turns the battery charger off. NOTE The Energy Saver System and Variable Module Management System mode commands are displayed only if enabled at the factory or by an Eaton Customer Service Engineer NOTE Variable Module Management System and Energy Saver System modes are mutually exclusive.
UPS is in Bypass mode. If Auto Bypass is not enabled, the UPS output remains off until the UPS transfers to Online mode. 7-12 EATON Power Xpert 164201716 Rev 3 www.eaton.com/powerquality 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
To enable Energy Saver System mode: NOTE The Energy Saver System mode commands are displayed only if enabled at the factory or by an Eaton Customer Service Engineer. NOTE The Variable Module Management System and Energy Saver System modes are mutually exclusive.
Menu To start High Alert mode: NOTE The High Alert mode commands are displayed only if enabled at the factory or by an Eaton Customer Service Engineer. NOTE The Variable Module Management System and Energy Saver System modes are mutually exclusive.
To enable Variable Module Management System mode: NOTE The Variable Module Management System mode commands are displayed only if enabled at the factory or by an Eaton Customer Service Engineer. NOTE The Variable Module Management System and Energy Saver System modes are mutually exclusive.
UPS Command Menu To start High Alert mode: NOTE The High Alert mode commands are displayed only if enabled at the factory or by an Eaton Customer Service Engineer. NOTE The Variable Module Management System and Energy Saver System modes are mutually exclusive.
To enable Energy Saver System mode: NOTE The Energy Saver System mode commands are displayed only if enabled at the factory or by an Eaton Customer Service Engineer. NOTE The Variable Module Management System and Energy Saver System modes are mutually exclusive.
Command Menu To start High Alert mode: NOTE The High Alert mode commands are displayed only if enabled at the factory or by an Eaton Customer Service Engineer. NOTE The Variable Module Management System and Energy Saver System modes are mutually exclusive.
To enable Variable Module Management System mode: NOTE The Variable Module Management System mode commands are displayed only if enabled at the factory or by an Eaton Customer Service Engineer. NOTE The Variable Module Management System and Energy Saver System modes are mutually exclusive.
Bypass Command Menu To start High Alert mode: NOTE The High Alert mode commands are displayed only if enabled at the factory or by an Eaton Customer Service Engineer. NOTE The Variable Module Management System and Energy Saver System modes are mutually exclusive.
Page 143
UPS is ready to transfer to Online mode and supply the critical load. NOTE To transfer to Online mode after starting individual UPMs, follow the procedure in paragraph 7.3.18. 7-21 164201716 Rev 3 www.eaton.com/powerquality Power Xpert 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
UPS Control Command menu bar. The UPM Control Command screen is displayed. 22. On the UPM Control Command screen, select UPM GO TO ONLINE 7-22 EATON Power Xpert 164201716 Rev 3 www.eaton.com/powerquality 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
The Online status indicator is illuminated. The UPS status indicates ONLINE. The UPM status indicates ONLINE. 7-23 164201716 Rev 3 www.eaton.com/powerquality Power Xpert 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
The System Status CONTROLS screen is displayed. If UPM 4 (FI-UPM) is installed, proceed to Step 3; otherwise, proceed to Step 7. 7-24 EATON Power Xpert 164201716 Rev 3 www.eaton.com/powerquality 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
UPM 1 Control Command screen is displayed. On the UPM Control Command screen, select UPM ON 10. Press the pushbutton on the UPM Command menu bar. SELECT 7-25 164201716 Rev 3 www.eaton.com/powerquality Power Xpert 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
Press the pushbutton on the main menu bar. The System Status CONTROLS screen is displayed. On the System Status screen, select the command. CHARGER 7-26 EATON Power Xpert 164201716 Rev 3 www.eaton.com/powerquality 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
CONTROLS Bypass Control Command screen is displayed. On the Control Command screen, select LOAD OFF Press the pushbutton on the Command menu bar. SELECT 7-27 164201716 Rev 3 www.eaton.com/powerquality Power Xpert 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
Page 150
W A R N I N G Power is present inside the UPS cabinet until the upstream input feeder circuit breaker is opened. 7-28 EATON Power Xpert 164201716 Rev 3 www.eaton.com/powerquality 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
NOTE The following instructions are for the Eaton-supplied REPO switch. If a customer-supplied REPO switch is used, it may not activate in the same manner; refer to the operating instructions provided with the switch.
UPS is in Bypass mode. If Auto Bypass is not enabled, the UPS outputs remain off until the UPSs transfer to Online mode. 7-30 EATON Power Xpert 164201716 Rev 3 www.eaton.com/powerquality 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
To enable Energy Saver System mode: NOTE The Energy Saver System mode commands are displayed only if enabled at the factory or by an Eaton Customer Service Engineer. NOTE The Variable Module Management System and Energy Saver System modes are mutually exclusive.
Menu To start High Alert mode: NOTE The High Alert mode commands are displayed only if enabled at the factory or by an Eaton Customer Service Engineer. NOTE The Variable Module Management System and Energy Saver System modes are mutually exclusive.
To enable Variable Module Management System mode: NOTE The Variable Module Management System mode commands are displayed only if enabled at the factory or by an Eaton Customer Service Engineer. NOTE The Variable Module Management System and Energy Saver System modes are mutually exclusive.
UPS Command Menu To start High Alert mode: NOTE The High Alert mode commands are displayed only if enabled at the factory or by an Eaton Customer Service Engineer. NOTE The Variable Module Management System and Energy Saver System modes are mutually exclusive.
To enable Energy Saver System mode: NOTE The Energy Saver System mode commands are displayed only if enabled at the factory or by an Eaton Customer Service Engineer. NOTE The Variable Module Management System and Energy Saver System modes are mutually exclusive.
Command Menu To start High Alert mode: NOTE The High Alert mode commands are displayed only if enabled at the factory or by an Eaton Customer Service Engineer. NOTE The Variable Module Management System and Energy Saver System modes are mutually exclusive.
To enable Variable Module Management System mode: NOTE The Variable Module Management System mode commands are displayed only if enabled at the factory or by an Eaton Customer Service Engineer. NOTE The Variable Module Management System and Energy Saver System modes are mutually exclusive.
Bypass Command Menu To start High Alert mode: NOTE The High Alert mode commands are displayed only if enabled at the factory or by an Eaton Customer Service Engineer. NOTE The Variable Module Management System and Energy Saver System modes are mutually exclusive.
Page 161
23. Repeat Steps 1 through 22 for each UPS in the distributed bypass system. NOTE To transfer to Online mode after starting individual UPMs, follow the procedure in paragraph 7.4.18. 7-39 164201716 Rev 3 www.eaton.com/powerquality Power Xpert 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
21. To transfer the UPM to Online mode, press the pushbutton on the CONTROLS UPS Control Command menu bar. The UPM Control Command screen is displayed. 7-40 EATON Power Xpert 164201716 Rev 3 www.eaton.com/powerquality 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
The Online status indicator is illuminated. The UPS status indicates ONLINE. The UPM status indicates ONLINE. 7-41 164201716 Rev 3 www.eaton.com/powerquality Power Xpert 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
The System Status CONTROLS screen is displayed. If UPM 4 (FI-UPM) is installed, proceed to Step 3; otherwise, proceed to Step 7. 7-42 EATON Power Xpert 164201716 Rev 3 www.eaton.com/powerquality 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
UPM Control Command screen is displayed. On the UPM Control Command screen, select UPM ON 10. Press the pushbutton on the UPM Command menu bar. SELECT 7-43 164201716 Rev 3 www.eaton.com/powerquality Power Xpert 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
Logic power remains on. Verify the battery breaker or disconnect for the UPS being shut down is open. If not, open the breaker. 7-44 EATON Power Xpert 164201716 Rev 3 www.eaton.com/powerquality 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
System Status Command menu bar. The CONTROLS UPM 1 Control Command screen is displayed. 14. On the UPM 1 Control Command screen, select UPM OFF 7-45 164201716 Rev 3 www.eaton.com/powerquality Power Xpert 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
11. Verify the External Communications Failure alarm has cleared and no other alarms are active on the online UPSs. 12. On the System Status screen, select the command. 7-46 EATON Power Xpert 164201716 Rev 3 www.eaton.com/powerquality 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
On the System Status screen, select the command. CHARGER Press the pushbutton on the System Status menu bar. The Charger CONTROLS Control Command screen is displayed. 7-47 164201716 Rev 3 www.eaton.com/powerquality Power Xpert 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
Restart the UPS after pressing the pushbutton by following the LOAD OFF procedure in paragraph 7.4.1 on page 7-30 or 7.4.8 on page 7-34. 7-48 EATON Power Xpert 164201716 Rev 3 www.eaton.com/powerquality 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
Page 171
7.4.1 on page 7-30 or 7.4.8 on page 7-34. W A R N I N G Power is present inside the UPS cabinet until the upstream input feeder circuit breaker is opened. 7-49 164201716 Rev 3 www.eaton.com/powerquality Power Xpert 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
NOTE The following instructions are for the Eaton-supplied REPO switch. If a customer-supplied REPO switch is used, it may not activate in the same manner; refer to the operating instructions provided with the switch.
LAN and telephone drops for use with X-Slot connectivity cards must be provided by facility planners or the customer. For installation and setup of an X-Slot card, contact an Eaton service representative (see page 1-10). Refer to the manual supplied with the X-Slot card for user instructions.
COMMUNICATION The eNotify Service relies on a ConnectUPS-X Web/SNMP Card (or Power Xpert card) installed with the UPS sending one-way status and event e-mails to Eaton Remote Monitoring servers that analyze and store the data. Those servers also take the appropriate actions of sending notifications and reports.
See paragraph 7.2 on page 7-2, “Using the Control Panel,” for instructions on navigating the control panel. EATON Power Xpert 164201716 Rev 3 www.eaton.com/powerquality 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
If a port is operating in Terminal mode and is connected to a computer, you can press [Esc] [H] to print the entire log with a firmware version header. The log in Terminal mode is always in English. 164201716 Rev 3 www.eaton.com/powerquality Power Xpert 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
RMP II contains backlit status indicators and a local horn. The RMP II can be flush‐mounted or surface‐mounted on a desktop, or secured to a wall. Figure 8‐3 shows an RMP II. Figure 8‐3. Remote Monitor Panel II 164201716 Rev 3 www.eaton.com/powerquality Power Xpert 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
Page 180
The UPS is preparing to shut down because the UPS is in Battery mode and the DC voltage is approaching its low limit. This indicator is accompanied by a horn. EATON Power Xpert 164201716 Rev 3 www.eaton.com/powerquality 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
Contacts are closed when approximately two minutes of battery time is remaining before the critical load is lost. UTILITY FAILURE Pins 6 and 15 Contacts are closed when Utility Failure is detected. 164201716 Rev 3 www.eaton.com/powerquality Power Xpert 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
TB2‐10 through TB2‐12 ON BATTERY TB2‐13 through TB2‐15 UPS ALARM TB2‐16 through TB2‐18 ON BYPASS TB2‐19 through TB2‐21 SHUTDOWN IMMINENT TB2‐22 through TB2‐24 8-10 EATON Power Xpert 164201716 Rev 3 www.eaton.com/powerquality 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
Eaton service representative. If the string requires service, refer to the battery manufacturer's operating manual for instructions on battery maintenance or contact an Eaton service representative. Observe these precautions when working on or around batteries: Remove watches, rings, or other metal objects.
Check the UPS air filters (located behind the front door and panels) and wash or replace as necessary. See Figure 9‐1 for filter locations. The ISBM filter sizes are 12” 20” 0.25” and the UPM filter size is 20” 44” 0.25”. Contact an Eaton service representative for replacement filters. To remove the filters: Remove one top screw and two bottom screws securing the UPM front panel (see Figure 4‐1 on page 4-3).
If the Field Installed UPM (FI-UPM) is installed, check the FI-UPM air filter (located behind the front panel) and wash or replace as necessary. See Figure 9‐2 for the filter location. The FI-UPM filter size is 20” 44” 0.25”. Contact an Eaton service representative for a replacement filter. To remove the filter:...
ANNUAL Maintenance Annual preventive maintenance should be performed only by authorized service personnel familiar with maintenance and servicing of the UPS system. Contact an Eaton service representative for more information about service offerings. EATON Power Xpert 164201716 Rev 3 www.eaton.com/powerquality...
Maintenance Training A basic training course, available from Eaton Corporation, gives you a competent working knowledge of the UPS system operation and teaches you how to perform first level corrective maintenance. For more information about training and other services, contact the Help Desk (see page 1-10).
Page 188
UPS MAINTENANCE This page intentionally left blank. EATON Power Xpert 164201716 Rev 3 www.eaton.com/powerquality 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
Configurable per UPM at nominal line voltage: Up to 120A with less than 85% load Up to 80A with 100% load Battery Shunt Trip 48 Vdc 10-1 164201716 Rev 3 www.eaton.com/powerquality Power Xpert 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
Meets IEC 801‐2 specifications. Withstands up to 25 kV pulse Immunity without damage and with no disturbance or adverse effect to the critical load. 10-2 EATON Power Xpert 164201716 Rev 3 www.eaton.com/powerquality 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual...
Page 191
Eaton-built battery cabinets (individually and collectively, the ”Warranted Items”) are free from defects in material and workmanship. If, in the opinion of Eaton, a Warranted Item is defective and the defect is within the terms of this Warranty, Eaton's sole obligation will be to repair or replace such defective item (including by providing service, parts, and labor, as applicable), at the option of Eaton.