CONNECTION OF THE POWER UNIT

4.2.3 Power unit terminal strips X1A, X1b

Terminal
X1A
L12, L22, L32
PA, –
X1B
PA, PB
PE
Table 12:
Power unit terminal strips housing C/S
Terminal
X1A
L12, L22, L32
+PA, –
X1B
+PA, PB
Connection for shielding/
PE
Table 13:
Power unit terminal strips housing G/W
All manuals and user guides at all-guides.com
The terminal strips meet the requirements of
Housing C/S
L12 L22
X1A
Function
Connection of the mains
supply via mains choke
Connection +/– DC link
Connection for braking
resistor
Connection for shielding/
earthing
PA corresponds to +PA, for housing C/S, + is not shown due to space reasons.
Housing G/W
X1A
L12 L22
L32
Function
Connection of the mains
supply via mains choke
Connection +/– DC link
Connection for braking
resistor
earthing
EN
L32
PA —
PB
X1b
Cross-section
10...25 mm²
AWG 8-2
0.5...16 mm²
AWG 10-2
Screw M5 for crimp con-
nector
X1b
+PA
Pb
Cross-section
M10 stud for ring crimp
connector
max. width 30 mm
60947-7-1.
Tightening torque
2 Nm
18 lb inch
Tightening torque
25 Nm
220 lb inch
43