14
|
Configuration
External input interlock settings overview
Parameter
B2 Delay Timer
B2 Reset Timer
Reset ON/OFF
Reset Mode
Reset Cool SP
Reset Heat SP
Window contact logic
Window contact B1
Contact closed (window
closed)
Installer and user reference guide
82
Description
Timer that starts as soon as
the key card is removed.
The unit continues normal
operation until the timer
expires.
Timer that starts as soon as
the Delay Timer expires.
When this timer expires,
the previous state (i.e.
regular setpoint) changes
to the "Default Reset
Setting" state.
"Default Reset Setting"
on/off state
"Default Reset Setting"
operation mode
"Default Reset Setting"
cooling setpoint
"Default Reset Setting"
heating setpoint
INFORMATION
When the value for a parameter is "- -", this means that when the timers expires,
nothing changes for that parameter and the current active value is kept.
Key card contact B2
Contact closed (key card
IN)
Possible values
0-10 minutes
0-20 hours
"ON", "OFF", "--"
Auto, Cooling, Heating, Fan
only, --
See indoor unit's setpoint
range and setpoint range
limitation, "--"
See indoor unit's setpoint
range and setpoint range
limitation, "--"
Time
Default value
"1 min"
"20 hours"
"OFF"
"--"
"22°C"
"22°C"
Action
Normal
indoor
operation.
The unit returns to the
previous
state
before
opening the contact.
BRC1H82W+K+S
Madoka wired remote controller
4P596268-1A – 2022.02
unit

Advertisement

Table of Contents
loading

This manual is also suitable for:

Madoka brc1h82wMadoka brc1h82s

Table of Contents