About the app
Setback
Installer and user reference guide
110
INFORMATION
In case of indoor unit setpoint logic, the system cannot run in Auto operation mode.
To enable Auto operation mode for VRV heat pump systems, go for remote
controller setpoint logic.
Enable Setback temperature control. Setback is a function that keeps the room
temperature in a specific range when the system is turned off (by the user, the
schedule function, or the OFF timer). To achieve this, the system temporarily runs
in Heating or Cooling operation mode, according to the setback setpoint and
recovery differential.
Example:
10ºC
12ºC
Settings
Heating
Heating
operation
setback
setpoint
Heating
recovery
differential
Cooling
Cooling
operation
setback
setpoint
Cooling
recovery
differential
INFORMATION
Setback is by default enabled.
Setback turns on the system for at least 30 minutes, unless the setback setpoint is
changed, or the system is turned on with the ON/OFF button.
When Setback is active, you cannot make changes to fan speed settings.
When Setback activates while the system is set to Auto operation mode, the
system will switch to Cooling or Heating operation mode, depending on which is
required. The Setback setpoint displayed on the operation screen is then
according to the operation mode.
When Setback is active and the "Home screen setpoint" setting is set to
"Symbolic", then there is no indication of Setback operation on the remote
controller home screen.
OFF
33ºC
35ºC
10°C
If the room temperature drops below
10°C, the system automatically starts
heating operation. If after 30 minutes
the temperature rises above 12°C, the
+2°
system stops heating operation, and
turns off again. When the room
temperature drops below 10°C again,
the process gets repeated.
35°C
If the room temperature rises above
35°C, the system automatically starts
cooling operation. If after 30 minutes
the temperature drops below 33°C, the
–2°C
system stops cooling operation, and
turns off again. When the room
temperature rises above 35°C again, the
process gets repeated.
Result
BRC1H82W+K+S
Madoka wired remote controller
4P596268-1A – 2022.02