Daikin Madoka BRC1H82K Installer And User Manual page 21

Wired remote controller
Hide thumbs Also See for Madoka BRC1H82K:
Table of Contents

Advertisement

Auto
BRC1H82W+K+S
Madoka wired remote controller
4P596268-1A – 2022.02
INFORMATION
In case of indoor unit setpoint logic, the system cannot run in Auto operation mode.
Therefore, to allow for Auto operation mode, go for remote controller setpoint logic.
For more information, see the Madoka Assistant app and
The Auto operation mode logic depends on the set setpoint logic (Madoka
Assistant app setting).
Single setpoint
C2
+ C1
SP
+ C1
C2
Cooling setpoint
Heating setpoint
DIFF Minimum setpoint differential between the Heating and the Cooling setpoint
+C1 Changeover setpoint (with guard timer)
C2 Forced changeover setpoint
0.5°C~2°C Field settable temperature intervals between setpoints
INFORMATION
The default value of the settable temperature range (0.5°C~2°C) is 0.5°C.
A changeover from the one operation mode to the other occurs in the following
cases:
Case 1: primary changeover ( +C1)
A changeover occurs from the moment the room temperature rises above/drops
below the Cooling/Heating changeover setpoint (C1), and the guard timer has run
out.
Example:
0.5°C
2°C
~
0.5°C
~
2°C
0.5°C
2°C
~
0.5°C
~
2°C
5
Operation
|
4
"Setpoint
logic" [
 108].
Dual setpoint
C2
0.5°C
2°C
~
+ C1
0.5°C
~
2°C
SP
DIFF
SP
0.5°C
2°C
~
+ C1
0.5°C
~
2°C
C2
Installer and user reference guide
21