In case of remote controller setpoint logic, choose whether to have single setpoint
logic, or dual setpoint logic.
Remote controller setpoint logic
Single setpoint
Dual setpoint
In case of dual setpoint logic, set the Minimum setpoint differential. This is the
minimum difference between the possible setpoints for Cooling and Heating
operation:
Cooling setpoint ≥ (Heating setpoint + Minimum setpoint differential)
Heating setpoint ≤ (Cooling setpoint – Minimum setpoint differential)
This means that:
If you lower the Cooling setpoint < (Heating setpoint + Minimum setpoint
differential), then the controller will automatically lower the Heating setpoint.
If you raise the Heating setpoint > (Cooling setpoint – Minimum setpoint
differential), then the controller will automatically raise the Cooling setpoint.
18º 19º 20º 21º 22º 23º 24º 25º 26º 27º 28º 29º
18º 19º 20º 21º 22º 23º 24º 25º 26º 27º 28º 29º
DIFF Minimum setpoint differential
INFORMATION
When the system is controlled by central control equipment, control of the system
by the controller is limited. When this is the case, it is not possible to set dual
setpoint logic in the Madoka Assistant app.
INFORMATION
When the indoor units are under control of a centralised controller, only indoor unit
setpoint logic is possible.
There is only one temperature setpoint,
independent of the operation mode. If
this is the case, changing the operation
mode does NOT change the setpoint. Or
the other way around, if you change the
setpoint, you do so for both Cooling and
Heating operation.
There are two temperature setpoints:
one specifically for Cooling operation,
and one specifically for Heating
operation. If this is the case, changing
the operation mode DOES change the
setpoint (i.e. to the setpoint of the other
operation mode). Or the other way
around, if you change the Cooling
setpoint, you do NOT change the
Heating setpoint.