Errors During Initialization - Omron SYSMAC CS1W-LCB01 Operation Manual

Loop control board
Hide thumbs Also See for SYSMAC CS1W-LCB01:
Table of Contents

Advertisement

Errors and Alarm Troubleshooting
Word
Bit
Name
A424
10
Partial Function
Block Database
(RAM) Error
During Simplex
Operation (non-
fatal error)
11
Backup Data
(Flash Mem-
ory) Error Flag
12
Specified EM
Bank Unusable
Error Flag
13 to
Not used.
14
15
Automatic
Recovery from
Cycle Offset
Flag (nonfatal
error)
7-1-2

Errors during Initialization

LED Indicators
LED
on front of
Indicator
Loop
on front of
Controller
CPU Unit
RDY
EXEC
ERR/ALM
(See note.)
Not lit
Not lit
Undeter-
mined
Not lit
Not lit
Lit
Not lit
Not lit
Lit
224
Changes to 1 (turns ON) when a database (RAM) error
occurs for some function blocks or when an error occurs
while restoring data from the Memory Card using the sim-
ple backup function when mounted to CS1D CPU Units
and operating in simplex mode or when mounted to CS1-H
CPU Units.
This flag is set to 1 (ON) when the parameter data stored in
flash memory has been corrupted.
This flag is set to 1 (ON) when specified EM bank is not a
usable bank.
---
If something unforeseen causes the cycle to the right or left
to be offset, duplex initialization is automatically executed
to restore synchronous operation. The flag is set to 1 (ON)
when recovery is achieved.
The following table lists errors that can occur during the initial processing per-
formed after the power is turned ON or the Inner Board is restarted.
Problem
Cause
Power sup-
The correct internal
ply problem
power supply is not
being supplied to the
Loop Controller.
The Loop Controller is
not mounted properly
in the CPU Unit.
The Loop Controller is
faulty.
Initial
The Loop Controller
recognition
was not recognized
error
properly by the CPU
Unit.
(Inner
Board
Stopped
Error)
Inner
A hardware error was
Board Error
detected (in memory or
elsewhere) during the
self-diagnostic test.
Explanation
Status
Operation is
None
stopped.
Operation is
None
stopped.
Operation is
None
stopped.
Section 7-1
Settings
1: Function block database
error during simplex opera-
tion or error while restoring
data.
0: Normal
1: Flash memory data
error
0: Normal
1: Cannot be used.
0: Can be used.
---
1: Duplex initialization exe-
cuted for synchronous dis-
placement recovery.
0: Normal
Error
Corrective action
code
(Stored
in error
log.)
Check the power supply volt-
age and verify that the correct
voltage is being supplied. Also,
check the PLC's total current
consumption.
Mount the Loop Control Board
securely. Replace the Loop
Control Board if the error
recurs after the Board is
secured and power is turned
ON again.
Turn the power OFF and ON
again. If the error occurs with a
Loop Control Board, replace
the Loop Control Board. If the
error occurs with the Loop
Controller component of a
Loop-control CPU Unit,
replace the entire Loop-control
CPU Unit.
Mount the Loop Control Board
securely. Replace the Loop
Control Board if the error
recurs after the Board is
secured and power is turned
ON again. If the error occurs
with the Loop Controller com-
ponent of a Loop-control CPU
Unit, replace the entire Loop-
control CPU Unit.
Turn the power OFF and ON
again. Replace the Loop Con-
trol Board if the error recurs. If
the error occurs with the Loop
Controller component of a
Loop-control CPU Unit,
replace the entire Loop-control
CPU Unit.