Omron SYSMAC CS1W-LCB01 Operation Manual page 131

Loop control board
Hide thumbs Also See for SYSMAC CS1W-LCB01:
Table of Contents

Advertisement

Description of Operation
Operations for hot starts, cold starts, and hot starts within specified time
Hot start mode (System Common block ITEM018 = 1)
CS and CJ Series
Power interruption
Cold start mode (System Common block ITEM018 = 2)
CS and CJ Series
Power interruption
Cold start
Parameters for control and operation blocks and
SPs for control blocks not held.
Hot start within specified time mode (System Common block ITEM018 = 0)
CS Series
Power interruption
Set value (1 h or less)
Hot start
CJ Series
Power interruption
Set value (1 h or less)
Hot start
Relationship with the
operation mode of the
CPU Unit
Hot start
Cold start for hot start within specified time mode
Parameters for control and operation blocks and
SPs for control blocks held.
Cold start for hot start within specified time mode
Parameters for control and operation blocks and
SPs for control blocks held.
The Loop Controller continues running regardless of the operation mode of
the CPU Unit.
CPU Unit operation mode
PROGRAM mode
RUN mode
MONITOR mode
24 hours
Normal cold start
Parameters for control and
operation blocks and SPs
for control blocks not held.
24 hours
24 hours
Normal cold start
Parameters for control and
operation blocks and SPs
for control blocks not held.
Running of Loop Controller
Running is continued.
Section 3-2
97