Omron SYSMAC CS1W-LCB01 Operation Manual page 89

Loop control board
Hide thumbs Also See for SYSMAC CS1W-LCB01:
Table of Contents

Advertisement

Specifications
Item
Internal
Number of control
Opera-
loops
tion
Number of opera-
tions for process
(excluding control)
Sequen-
Step lad-
tial control
ders
(Use only
one or the
other)
Sequence
tables
Control
PID control
method
Possible control type
combinations
Alarm
Integrated into PID
block
Alarm block
Internal analog signal
Operating status monitor
method
The maximum number of loops that can be used if the LCB load rate is 80% for a stan-
dard applications (e.g., with each loop consisting of one Ai4 Terminal, Segment Linear-
izer, Basic PID, and A04 terminal) is shown in the following table.
CS1W-LCB01/05 (LCCB01/05)
Operation cycle: Maximum number of loops
0.01 s: 20 loops
0.1 s: 100 loops
1 s: 250 loops
CS1D-CPU@@P (LCB05D)
Operation cycle: Maximum number of loops
0.1 s: 80 loops
1 s: 250 loops
CJ1W-CPU43P/44P/45P (LCB03)
Operation cycle: Maximum number of loops
0.01 s: 20 loops
0.1 s: 100 loops
1 s: 150 loops
CJ1W-CPU42P (LCB01)
Operation cycle: Maximum number of loops
0.01 s: 20 loops
0.1 s: 25 loops
1 s: 25 loops
LCB01: Max. 50 blocks
LCB03: Max. 30 blocks
LCB05: Max. 500 blocks
LCB01: 20 blocks per Board and total max. 2,000 commands per Board
LCB03/05/05D: 200 blocks per Board and total max. 4,000 commands per Board
Loop Controllers common: Divisible to 100 commands max. per block and 100 steps
max. per block (100 commands max. per step)
Sequence tables: 200 max. (LCB05 and 05D only)
PID with two degrees of freedom
Basic PID control, cascade control, feedforward control, sample PI control, dead time
compensation, PID control with differential gap, override control, program control, time-
proportional control and other control types can be achieved by combining function
blocks.
4 PV alarms (high/high limit, high limit, low limit, low/low limit) per PID block, 1 deviation
alarm
High/Low Alarm block, Deviation Alarm block
Min. −320.00% to max. +320.00%
Scaling of the engineering units depends on the CX-Process Tool (sold separately).
Executed by commercially available SCADA software. In the SCADA software, tags set
on the CX-Process Tool are specified.
Description
0.02 s: 35 loops
0.2 s: 180 loops
2 s: 250 loops
0.2 s: 140 loops
2 s: 250 loops
0.02 s: 35 loops
0.2 s: 150 loops
2 s: 150 loops
0.02 s: 25 loops
0.2 s: 25 loops
2 s: 25 loops
Section 1-3
0.05 s: 70 loops
0.5 s: 250 loops
0.5 s: 250 loops
0.05 s: 70 loops
0.5 s: 150 loops
0.05 s: 25 loops
0.5 s: 25 loops
55