Omron SYSMAC CS1W-LCB01 Operation Manual page 247

Loop control board
Hide thumbs Also See for SYSMAC CS1W-LCB01:
Table of Contents

Advertisement

Description of FINS Commands
Response code
Response code
0000 Hex
Normal completion
1001 Hex
Command length over
• The command length exceeds 2002 bytes.
1002 Hex
Insufficient command length
• The command length is less than four bytes.
1003 Hex
Number of elements/number of data mismatch
• The number of data items does not match the number of
ITEMs.
1101 Hex
No type
• An unusable block address was specified in the parameter
type.
• The block address specified in the parameter type is an
unregistered function block.
• Function blocks other than System Common blocks cannot
be accessed as the RAM has not yet been initialized
(cleared) after a battery failure causes content of RAM to be
lost.
1103 Hex
Specified address out-of-range error
• The start address contains a non-existent ITEM.
• An attempt was made to write to the format setting of a Sys-
tem Common block.
110C Hex
Other item parameter error
• Number of ITEMs is 0.
• The specified data length does not match the actual data of
each ITEM specified by the write start address.
• The combination of block address and block format is forbid-
den.
• Write data is out of the data range for each ITEM.
2605 Hex
Service in operation
The function block data in the Loop Controller was replaced,
and then the LCB started operation without restarting the LCB
restart or cycling the PLC power supply. (An attempt was
made to write 1 or 2 to the System Common Block ITEM 014
(run/stop command).)
Section 6-3
Meaning