Chapter 5 Display And Setting Of Various Functions; List Of Functions - SMC Networks HRR050-A 20 Series Operation Manual

Thermo-chiller
Hide thumbs Also See for HRR050-A 20 Series:
Table of Contents

Advertisement

Chapter 5 Display and Setting of
Various Functions
Read and understand this manual carefully before changing the
settings.

5.1 List of Functions

No.
Item
1
Main menu
Basic setting mode
2
Alarm display menu
3
Maintenance notification menu
4
Monitor Menu
5
Standard setting menu
6
Alarm setting menu
Advanced setting
7
Communication setting menu
mode
8
Reset menu
9
Information monitor menu
10
Alarm history menu
HRR Series
The product can have the displays and settings shown in Table 5-1.
Table 5-1
List of functions
Displays the current temperature and set temperature of circulating fluid.
Change circulating fluid setting temperature.Set the pump output (400V type only).
By pressing the [▲] [▼] key, circulating fluid return temperature,
circulating fluid discharge pressure, circulating fluid flow rate(except option Z, Z1),
pump output setting (400V type only), electric conductivity (option DM only) are displayed.
When an alarm occurs, the alarm number is displayed.
Only the currently occurring alarms are displayed.
Notification function of maintenance time. When pump, fan, refrigerator,
dustproof filter, DI filter is replaced, it is displayed.
Displays the temperature of the freezing circuit, pressure and
ambient temperature (air-cooled type only).
Set various setting values such as key lock, alarm buzzer sound,
offset temperature, electric conductivity set value (in option DM).
It sets the validity / invalidity of various alarms, switches WRN (operation continuation) /
FLT (operation stop), and changes the alarm set value.
Set contact input / output and serial communication.
Initialize the setting data and reset the maintenance time.
The model and program version of this product are displayed.
Displays the operation cumulative time, pump operation cumulative time,
cumulative freezer operation cumulative time, fan operation cumulative time,
dust filter use time, and DI filter usage time for this product.
The alarm number that occurred in the past and the operation total time when
an alarm occurred are displayed. (Up to 150 records will be recorded.)

Chapter 5 Display and Setting of Various Functions

Outline
HRX-OM-X071
Reference
page
5.4.2
5.4.3
5.4.4
5.5.2
5.5.3
5.5.4
5.5.5
5.5.6
5.5.7
5.5.8
5.1 List of Functions