Electric conductivity setting value
The set value of electric conductivity can be set within the range of "0.5 to 45.0
μS / cm".The initial value is "25.0 μS / cm".
When the [ENT] key is pressed, the set value flashes. Press the [▲], [▼] key to
change the set value. When the [ENT] key is pressed, the flashing ends
and the set value is confirmed.
Electric conductivity hysteresis
10.
Press the [▼] key. Displays electric conductivity hysteresis setting screen.
* Displayed only when option DM [With electric conductivity control function, Applicable to
DI water piping] is selected.
RUN
Electric conductivity hysteresis
The electric conductivity control hysteresis can be set within a range of "0.1 to 10.0
μS / cm" . The initial value is "5.0 μS / cm".
For the control image of electric conductivity by hysteresis, refer to "6.1 Option DM
[With electric conductivity control function, Applicable to
DI water piping].
To change the setting value, press the [ENT] key. Hysteresis set value flashes,
press the [▲], [▼] key to change the set value.
When the [ENT] key is pressed, the flashing ends and the set value is confirmed.
11.
Press the [▼] key. Display as shown below. It is not used with this product.
RUN
12.
Press the [▼] key. Display as shown below. It is not used with this product
RUN
HRR Series
Electric conductivity control hysteresis set value Unit: μS / cm
Unused
EXT ⇒ CTRL( Alternately displayed )
Unused
EXT ⇒ OFSET( Alternately displayed )
Chapter 5 Display and Setting of Various Functions
HRX-OM-X071