The water cooled product radiates heat to the facility water.
It is necessary to supply the facility water. Please prepare the facility
water system that satisfies the heat radiation and the facility water
specifications below.
Required facility water system (for water cooled type)
Model
Radiated
HRR050-W
-20-
Approx.10
HRR050-W
-40-
HRR Series
Facility water source to be prepared
Table 3-2
Heat
Facility water temp.
range
o
C
kW
5 to 40
(Rating 25)
5 to 35
(Rating 25)
Chapter 3 Transport and Setting Up
Required facility water flow rate
l/min
Facility water temprature
25℃
32℃
16
19
16
19
HRX-OM-X071
35℃
40℃
-
27
22
-
3.2 Installation
3-5