Contact output signal 1 Select maintenance
16.
Press the [▼] key. Displays screen for setting the selected maintenance for the
Contact output signal 1. The alarm is valid when the "selected maintenance status
signal output" is active.
Select the maintenance alarm No. to be allocated to Contact output signal 1.
●Setting range: MT.01 to MT.05 (Initial value: MT.01)
Contact output signal 2 Select function
17.
Press the [▼] key. Displays screen for setting the function for the Contact output signal
2.
Displays the function for the Contact output signal 2.
Set value
OFF
No output signal
RUN
Operation status signal output
RmT
Remote status signal output
EXTC
Unused
RDY
Ready completion (TEMP READY) signal output
TOUT
TEMP OUT (temperature is out of the range) signal output
FLT
FLT (operation stop) alarm signal output
WRN
WRN (operation continue alarm) signal output
mANT
Notice for maintenance signal output
ALm
Alarm status signal output
SW1
Pass through signal of the contact input signal 1
SW2
Pass through signal of the contact input signal 2
ASEL
Selected alarm status signal output
mSEL
Selected notice for maintenance signal output
HRR Series
Chapter 5 Display and Setting of Various Functions
Contact output signal 1 Selected maintenance alarm No.
DOUT1 ⇒ MANT ⇒ CODE( Alternately displayed )
Contact output signal 2 function
DOUT2 ⇒ SEL( Alternately displayed )
Explanation
HRX-OM-X071
Initial value
(Default setting)
5.5 Advanced setting mode