Chapter 9 Documents
9.1 Specifications
9.1.1 HRR050-A--
Model
Cooling method
Refrigerant
Quantity of refrigerant
Control method
Ambient temperature andhumidity
1 2
and altitude
Circulating fluid
Operating temperature
1
range
Cooling capacity (50/60Hz)
Heating capacity
(50/60Hz)
Temperature stability
Pump capacity (50/60Hz)
Pump capacity of option T1
7
Pump capacity of option T2
7
Rated fiow (50/60Hz)
Rated fiow of option T1
8
Circulating
Rated fiow of option T2
8
fluid
system
Flow display range
Electric conductivity
display range
Electric conductivity
setting range
Particle filter nominal
filtration rating
Bypass valve
Tank capacity
Fluid outlet , fluid
return port port size
Drain port size
Leakage protection
Fluid contact part material
Power supply
Circuit protector
Electrical
Applicable earth leakage breaker
system
Cable Qty x size(Inculding ground)
Rated operating current
16
(50/60Hz)
Rated power consumption
16
(50/60Hz)
Communication function
17
Noise level (50/60Hz)
18
Dimensions
19
Accessory
Weight
20
1: No condensation should be present. During seasons or in locations where the ambient temperature is likely to fall
below freezing point, please contact SMC.
HRR Series
Table 9-1 Specifications [HRR050-A-20/40-]
HRR050-A -20-
kg
Temperature:5 to 40℃,Humidity:30 to 70%,Altitude: Less than 3000m
*3
℃
4
W
W
5
6
℃
7
MPa
0.34(at 15L/min)/ 0.34(at 23L/min)
MPa
MPa
8
L/min
L/min
L/min
9
L/min
µS/cm
µS/cm
µm
10
10
L
Stainless steel, Copper brazing (Heat exchanger)
Aluminum oxide ceramic,Carbon,PP,PE,POM,PA,FKM,EPDM,PVC,
Single-phase 200 to 230VAC 50/60Hz
Allowable voltage range +/-10%
A
Rated current:20A
12
Sensitivity current:30mA
15
3core×12AWG(3 core×3.5mm
A
kW
(kVA)
dB(A)
mm
Power supply connector,Maintenance handle for particle filter
kg
Air-Cooled refrigerated type
R410A(HFC)
0.72
PID control
Tap water, 15% ethylene glycol aqueous solution
5 to 35
4600/ 5100
1000/ 1200
±0.1
-
-
15/ 23
-
-
5 to 40
0.1 to 48(For option -DM)
0.5 to 45(For option -DM)
5
Installed
Approx.5
Rc1/2
Rc1/4,With cap
Drain pan structure (With water leakage detector
12
PPS,AS,fluoropolymer
13
20
2
)
9.3/ 11.8
1.9/ 2.4(1.9/ 2.5)
Contact input/ output, Serial RS-485/ RS-232C
63/ 67
W483xD550xH710
Operation manual,Particle filter element
74
HRX-OM-X071
Chapter 9 Documents
HRR050-A -40-
0.74
4800/ 5800
1100/ 1200
-
0.35(at 16L/min)
0.40(at 24L/min)
-
16
24
10
)
11
11
,Bronze
,SiC,
12
,Ion exchange resin
3-phase 380 to 415VAC (50/ 60Hz)
Allowable voltage range +/-10%
3-phase 460 to 480VAC (60Hz)
Allowable voltage range +4%, -10%
10
Rated current:10A
Sensitivity current:30mA
4core×14AWG(4 core×2.0mm
4.4/ 4.1(For option T1)
4.9/ 4.5(For option T2)
2.2/ 2.5 (3.1/ 2.9) (For option T1)
2.4/ 2.7 (3.6/ 3.1) (For option T2)
70/ 70
10
,
10
67
9.1 Specifications
13
13
2
)
9-1
Need help?
Do you have a question about the HRR050-A 20 Series and is the answer not in the manual?