HRX-OM-X071
Chapter 9 Documents
2: If the product is used at an altitude of 1000 m or higher, refer to " Thermo-chiller installation in high altitude of 1000
meters or more" on page 3-3.
3: If tap water is used, use water that is compliant with the Water Quality Standards of the Japan Refrigeration and Air
Conditioning Industry Association (JRA GL-02-1994 cooling water system - circulating type - make-up water).
4: (1)Ambient temp.: 25℃, (2) Circulating fluid temp: 20℃, (3) Criculating fluid at the rated flow,(4) Criculating fluid :
Tap water, (5)Power supply : 200V type:AC200V, 400V type : AC400V, (6)Piping length : Shortest . For option
T2(High pressure inverter pump), the cooling capacity is reduced by 400W.
5: (1)Ambient temp: 25℃, (2) Circulating fluid temp: 20℃, (3) Criculating fluid at the rated flow,(4) Criculating fluid :
Tap water, (5)Power supply : 200V type:AC200V, 400V type : AC400V, (6)Piping length : Shortest .
6: Temperature at the thermo-chiller outlet when the circulating fluid flow is at the rated flow and the circulating fluid
outlet and return port are directly connected.
The installation environment and power supply are within the specification range and stable.
7: The capacity at the thermo-chiller outlet when the circulating fluid temp. is 20℃.
8: The required flow rate for maintaining the cooling capacity or temperature stability.
The specification of the cooling capacity and the temperature stability may not be satisfied if the flow rate is lower
than the rated flow.
9
Not included for options - Z and -Z1.
10: Not included for options -Z.
11: Options M (Applicable to DI water piping) and DM (Electric conductivity control + Applicable to deionized water
piping) do not contain copper or bronze.
12: For Option DM (With electric conductivity control function + Applicable to DI water piping).
13: Max. voltage less than 500V and no continuous voltage flucuation.
14: Purchase an earth leakage breaker with a sensitivity current of 30 mA and a power supply of AC200 V separately.
15: To be prepared by the customer.
16: (1)Ambient temp: 25℃, (2)Circulating fluid temp: 20℃, (3) Circulating fluid at the rated flow, (4) Circulating
fluid :Tap water, (5)Power supply: 200V type:AC200V, 400V type : AC400V, (6)Piping length: Shortest, (7) With
the rated cooling load applied.
17: Front: 1 m, height: 1 m, stable with no load, Other conditions → See ∗3.
18: Dimension between panels. Projection is not included.
When option Y[With feet, and no Rack Mounting bracket] is selected, refer to [6.4. Option Y (With feet and no
Rack Mounting bracket)].
19: For Option DM (With electric conductivity control function + Applicable to DI water piping), a DI filter is included.
For pipe thread type F, a G thread conversion fitting set is included.
For pipe thread type N, an NPT thread conversion fitting set is included.
20: Weight in the dry state without circulating fluids The weight will increase by 1 kg when Option DM (With electric
conductivity control function + Applicable to DI water piping) is selected.
The product weight decreases by 1 kg for Option-Z.