Page 3
Safety of Persons • The system has its own power source (the battery). Consequently, the power outlets may be energized ven if the systems is disconnected from the AC power source. Dangerous voltage levels are resent within the system. It should be opened exclusively by qualified service personnel.
Page 4
During the replacement of the Battery Module, it is imperative to use the same type and number of element as the original Battery Module provided with the UPS to maintain an identical level of performance and safety. If there are any questions, don’t hesitate to contact your local EATON representative.
6 6 U U P P S S M M a a i i n n t t e e n n a a n n c c e e ....................................................... . 3 3 3 3 6.1 Storing the Equipment ..........................33 Eaton 9PX Lithium-Ion P-164001006—Rev 01...
Page 6
8 8 S S p p e e c c i i f f i i c c a a t t i i o o n n s s ......................................................... . 4 4 1 1 8.1 Model Specifications ..........................41 Eaton 9PX Lithium-Ion P-164001006—Rev 01...
Before installing your 9PX, please read the booklet presenting the safety instructions. Then follow the indications in this manual. To discover the entire range of EATON products and the options available for the 9PX range, invite you to visit our web site at Eaton.com...
Page 8
With the Eaton 9PX, you can safely eliminate the effects of power disturbances and guard the integrity of your equipment. Providing outstanding performance and reliability, the Eaton 9PX’s unique benefits include: •...
23.8 x 17.3 x 3.4 / 605 x 440 x 86.5 50.2 / 22.8 9PXEBM48RT-L 17.6 x 17.2 x 1.7 / 448 x 438 x 42.9 36.5 / 16.6 9PXEBM72RT-L 23.7 x 17.2 x 1.7 / 603 x 438 x 42.9 46.6 / 21.2 Eaton 9PX Lithium-Ion P-164001006—Rev 01...
USB communication port Connector for ROO (Remote On/Off) control and RPO (Remote Power Off) 9PX 3000RT-L (*) (*) Primary and Grouped outlets ) are protected by 20A circuit breakers. 9PX 1500GRT-L 9PX 2200GLRT-L & 9PX 3000GRT-L Eaton 9PX Lithium-Ion P-164001006—Rev 01...
C C o o n n t t r r o o l l P P a a n n e e l l The UPS has a five-button graphical LCD. It provides useful information about the UPS itself, load status, events, measurements and settings. Eaton 9PX Lithium-Ion P-164001006—Rev 01...
L L C C D D D D e e s s c c r r i i p p t t i i o o n n Operation status Online mode 100% 100% 2.4kW 19min Load/equipment status Battery status 3.0kVA 1EBM Efficiency: 94% Ef ciency and load group information Eaton 9PX Lithium-Ion P-164001006—Rev 01...
[Efficiency] % / [Battery] % min V n° EBM / [Battery remaining life] months / [Average power usage] Wh / [Cumulated power] Wh / BMS Information Control Go to Bypass Transfers the UPS on Bypass mode Eaton 9PX Lithium-Ion P-164001006—Rev 01...
IPv4], [Com card IPv6], [Com card MAC] Registration Links to Eaton registration website 2 2 . . 7 7 U U s s e e r r S S e e t t t t i i n n g g s s The following table displays the options that can be changed by the user.
[Enabled] [Disabled] [Timer] [10s] … [180s] On/Off Settings [Enabled] When mains recover during a Forced reboot shutdown sequence: If set to Enabled, [10s] shutdown sequence will complete and wait 10 seconds prior to restart, If set Eaton 9PX Lithium-Ion P-164001006—Rev 01...
If you ordered an optional Extended Battery Module (EBM), verify that the following additional items are included with the EBM: Battery power cable with attached battery detection cable Stabilizer bracket (4 screws included) Rack kit for 19-inch enclosures (optional) EBM Installation manual. Eaton 9PX Lithium-Ion P-164001006—Rev 01...
A small amount of arcing may occur when connecting the internal batteries. This is normal and will not harm personnel. Connect the cables quickly and firmly. Connect the two battery connectors together. Put back the front panel, then clip the center cover. Eaton 9PX Lithium-Ion P-164001006—Rev 01...
If installing additional cabinets, place them next to the UPS in their final location. • Adjustment of the orientation of the LCD panel and of the logo. • Adjustment of the angle of vision of the LCD panel. Eaton 9PX Lithium-Ion P-164001006—Rev 01...
R R a a c c k k I I n n s s t t a a l l l l a a t t i i o o n n • Rack mounting of UPS, EBM, and accessory modules. Follow steps 1 to 4 for module mounting on the rails. The rails and necessary hardware are supplied by EATON. Eaton 9PX Lithium-Ion P-164001006—Rev 01...
Battery Comm EBM 4 NOTE The EBM communication wiring connections are directional and must be connected in the correct sequence to ensure proper detection, regulation and lifecycle monitoring of the integrated battery management system (BMS). Eaton 9PX Lithium-Ion P-164001006—Rev 01...
D D e e t t e e c c t t i i n n g g o o t t h h e e r r A A c c c c e e s s s s o o r r i i e e s s Tip If you ordered other UPS accessories, refer to specific user manuals to check the connection to the UPS. Eaton 9PX Lithium-Ion P-164001006—Rev 01...
Note. The UPS charges the battery as soon as it is connected to the AC-power source, even if button is not pressed Once the UPS is connected to the AC-power source, eight hours of charging are required before the battery can supply the rated backup time. Eaton 9PX Lithium-Ion P-164001006—Rev 01...
LOAD * 9PX 1500RT-L: To connect to MBP-115, 9PX 3000RT-L follow the same procedure as for the 9PX 2000RT / 9PX 3000RT. MBP-130 35 36 LOAD Eaton 9PX Lithium-Ion P-164001006—Rev 01...
Page 28
"UPS ON - OK to switch" on the HotSwap MBP module goes ON. HotSwap MBP module test 1. Set switch to Bypass position and check that the load is still supplied. 2. Set switch back to Normal position. Eaton 9PX Lithium-Ion P-164001006—Rev 01...
USB or RS232 communication port on the UPS. The UPS can now communicate with EATON power management software. Installation of the communication cards It is not necessary to shutdown the UPS before installing a communication card.
To ensure the UPS stops supplying power to the load during any mode of operation, the input power must be disconnected from the UPS when the Remote Power Off function is activated. Leave the RPO connector installed in the RPO port on the UPS even if the RPO function is not needed. Eaton 9PX Lithium-Ion P-164001006—Rev 01...
Page 31
UPS from the front panel. Normally Closed Plug the RPO connector into the back of the UPS and fix the screws. Connect and restart the UPS according to the previously described procedures. Eaton 9PX Lithium-Ion P-164001006—Rev 01...
Page 32
INDGW-M2 card- has SNMP and HTTP capabilities and a Modbus to facilitate remote monitoring of the UPS system through any Building Management System. • Relay-MS card- has isolated dry contact (Form-C) relay outputs for UPS status: Utility failure, Battery Eaton 9PX Lithium-Ion P-164001006—Rev 01...
Page 33
UPS or power information. If there is a power outage and the 9PX UPS battery power becomes low, Eaton Software suite can automatically shut down your computer system to protect your data before the UPS shutdown occurs.
O O p p e e r r a a t t i i n n g g M M o o d d e e s s The Eaton 9PX front panel indicates the UPS status through the UPS indicators, see section 2.4 Control Panel...
10 ms when utility fails. Transfers to High Efficiency mode will be active after 5 minutes of Bypass voltage monitoring: if Bypass quality is not in tolerance, then the UPS will remain in Online mode. Eaton 9PX Lithium-Ion P-164001006—Rev 01...
Configuring Bypass Settings Eaton recommends to use the HE mode only to protect IT equipment. To set the High Efficiency mode: Select Settings, In/Out settings, and High Efficiency mode. Select Enabled and Enter to confirm. The UPS transfers to High Efficiency mode after 5 minutes.
5 5 . . 1 1 0 0 R R e e t t r r i i e e v v i i n n g g t t h h e e F F a a u u l l t t L L o o g g To retrieve the Fault log through the display: Press any button to activate the menu options, then select Fault log. Scroll through the listed faults. Eaton 9PX Lithium-Ion P-164001006—Rev 01...
If you store the equipment for a long period, recharge the battery every 6 months by connecting the UPS to utility power. The internal batteries charge to 90% capacity in less than 3 hours. However, Eaton recommends that the batteries charge for 48 hours after long-term storage. Check the battery recharge date on the shipping carton label.
Unplug the EBM power cable and battery detection cable from the UPS. If additional EBM(s) are installed, unplug the EBM power cable and battery detection cable from each EBM. Replace the EBM(s). See "Recycling the used equipment" for proper disposal. Eaton 9PX Lithium-Ion P-164001006—Rev 01...
R R e e c c y y c c l l i i n n g g T T h h e e U U s s e e d d E E q q u u i i p p m m e e n n t t Contact your local recycling or hazardous waste center for information on proper disposal of the used equipment. Eaton 9PX Lithium-Ion P-164001006—Rev 01...
Eaton, Powerware, and BladeUPS are registered trademarks of Eaton Corporation or its subsidiaries and affiliates. Phillips and Pozidriv are registered trademarks of Phillips Screw Company. ECopyright 2008–2010 Eaton Corporation, Raleigh, NC, USA. All rights reserved. No part of this document may be reproduced in any way without the express written approval of Eaton Corporation.
Page 43
T T y y p p i i c c a a l l A A l l a a r r m m s s a a n n d d F F a a u u l l t t s s The Eaton 9PX are designed for durable, automatic operation and also alert you whenever potential operating problems may occur.
UPS technical representative. Please have the following information ready when you call for service: • Model number • Serial number • Firmware version number • Date of failure or problem • Symptoms of failure or problem • Customer return address and contact information Eaton 9PX Lithium-Ion P-164001006—Rev 01...
C C E E C C o o m m p p l l i i a a n n c c e e C C o o n n t t a a c c t t • Eaton I.F. SAS - 110 Rue Blaise Pascal - 38330 Montbonnot St Martin – France. Eaton 9PX Lithium-Ion...
Page 46
CE Compliance Contact Eaton 9PX Lithium-Ion P-164001006—Rev 01...
Page 47
17.7 x 17.3 x 3.4 / 450 x 440 x 86.5 34.8 / 15.8 9PX2200GRT-L 23.8 x 17.3 x 3.4 / 605 x 440 x 86.5 48.6 / 22.1 9PX3000GRT-L 23.8 x 17.3 x 3.4 / 605 x 440 x 86.5 50.2 / 22.8 Eaton 9PX Lithium-Ion P-164001006—Rev 01...
98% for 2K G models 90% fo r 2K G models 94% for 3K G models 97.2% for 3K LV models 86% for 3K LV models 98% for 3K G models 89% for 3K G models Eaton 9PX Lithium-Ion P-164001006—Rev 01...
Page 50
< 47 dBA at 1 meter typical for 2K et 3K models < 40 dBA at 1 meter typical for 70, 1K et 1K5 models * 9PX1500RT-L, 9PX2000RT-L, 9PX3000RT-L, 9PX1500GRT-L, 9PX2200GRT-L, 9PX3000GRT-L have CE/ cULus/Energy Star/ BSMI. 9PXEBM48RT-L, 9PXEBM72RT-L have CE / cULus / NOM. Eaton 9PX Lithium-Ion P-164001006—Rev 01...
Page 51
Lithium Iron Phosphate (LFP) battery module Lithium-Ion float service life 8 years /25°C Monitoring Integrated battery management system (BMS) for temperature regulation and life cycle monitoring. EBM Battery Cable Length 350 mm / 13.78 in Eaton 9PX Lithium-Ion P-164001006—Rev 01...