Controls: Close - AUMA SQ 14.2 Operation Instructions Manual

Part-turn actuators with actuator controls
Hide thumbs Also See for SQ 14.2:
Table of Contents

Advertisement

SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2
AM 01.1
Disable EMERGENCY
command
10.8.

Controls: close

Figure 39: Interface board for available option EMERGENCY - OPEN/EMERGENCY
- CLOSE
[B1]
Link available: EMERGENCY - CLOSE
[B2]
Link available: EMERGENCY - OPEN
1.
Remove face plate.
2.
Disconnect links [B1] or [B2].
Danger of corrosion due to damage to paint finish!
→ Touch up damage to paint finish after work on the device.
1.
Clean sealing faces of housing and cover.
2.
Check whether O-ring [3] is in good condition, replace if damaged.
3.
Apply a thin film of non-acidic grease (e.g. petroleum jelly) to the O-ring and
insert it correctly.
4.
Place cover [1] on switch compartment.
5.
Fasten screws [2] evenly crosswise.
Commissioning – controls settings