SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2
AM 01.1
9.11.

Mechanical position indicator: set

9.12.

Switch compartment: close

9.
Approach end position CLOSED again and check minimum value (0.1 mA or
4.1 mA). If necessary, correct the setting.
1.
Place indicator disc on shaft.
2.
Move valve to end position CLOSED.
3.
Turn lower indicator disc until symbol
mark
on the cover.
4.
Move actuator to end position OPEN.
5.
Hold lower indicator disc in position and turn upper disc with symbol
until it is in alignment with the mark
6.
Move valve to end position CLOSED again.
7.
Check settings:
If the symbol
(CLOSED) is no longer in alignment with mark
Repeat setting procedure.
Danger of corrosion due to damage to paint finish!
→ Touch up damage to paint finish after work on the device.
1.
Clean sealing faces of housing and cover.
2.
Check whether O-ring [3] is in good condition, replace if damaged.
3.
Apply a thin film of non-acidic grease (e.g. petroleum jelly) to the O-ring and
insert it correctly.
4.
Place cover [1] on switch compartment.