AUMA SQ 14.2 Operation Instructions Manual page 59

Part-turn actuators with actuator controls
Hide thumbs Also See for SQ 14.2:
Table of Contents

Advertisement

SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2
AM 01.1
Service conditions
Use
Mounting position
Installation altitude
Ambient temperature
Enclosure protection according
to EN 60529
Pollution degree
Vibration resistance according
to IEC 60068-2-6
Corrosion protection
Finish coating
Colour
Lifetime
Further information
EU Directives
Indoor and outdoor use permissible
Any position
2,000 m above sea level
> 2,000 m above sea level, please contact AUMA
Standard:
–40 °C to +80 °C (part-turn actuators for open-close duty with 3-phase AC mo-
tors)
–40 °C to +70 °C (part-turn actuators for open-close duty with 1-phase AC mo-
tors)
–40 °C to +60 °C (part-turn actuators for modulating duty)
Options:
–60 °C to +60 °C
0 °C to +120 °C (part-turn actuators for open-close duty with 3-phase AC motors)
For actual version, refer to actuator name plate.
Standard:
NEMA type 6P with AUMA 3-phase AC motor/1-phase AC motor
F
Option:
DS Terminal compartment additionally sealed against interior (double sealed)
According to A
following requirements:
Depth of water: maximum 8 m head of water
Duration of continuous immersion in water: Max. 96 hours
Up to 10 operations during continuous immersion
Modulating duty is not possible during continuous immersion.
For actual version, refer to actuator name plate.
Pollution degree 4 (when closed) according to EN 50178
2 g, from 10 to 200 Hz
Resistant to vibration during start-up or for failures of the plant. However, a fatigue strength
may not be derived from this. Valid for part-turn actuators in version AUMA NORM (with
AUMA plug/socket connector, without actuator controls). Not valid in combination with
gearboxes.
Standard:
KS: Suitable for installation in industrial units, in water or power plants with a
low pollutant concentration as well as for installation in occasionally or perman-
ently aggressive atmosphere with a moderate pollutant concentration (e.g.
wastewater treatments plants, chemical industry)
Option:
KX: Suitable for installation in extremely aggressive atmospheres with high hu-
midity and high pollutant concentration
KX-G : same as KX, however aluminium-free version (outer parts)
Powder coating
Standard:
AUMA silver-grey (similar to RAL 7037)
Option:
Other colours are possible on request.
AUMA part-turn actuators meet or even exceed the lifetime requirements of EN 15714-2.
Detailed information can be provided on request.
Electromagnetic Compatibility (EMC): (2004/108/EC)
Low Voltage Directive: (2006/95/EC)
Machinery Directive: (2006/42/EC)
ering enclosure protection: refer to name plate.
Technical data
59