Summary of Contents for Eaton 93E Series

  • Page 1 Eaton ® ® 93E UPS Generation 3 20–30 kVA (208/220V) Installation and Operation Manual p/n: 164000301 Revision 04...
  • Page 2 National Fire Protection Association, Inc. ERIFLEX and FLEXIBAR are registered trademark of Erico International Corporation. All other trademarks are property of their respective companies. ©Copyright 2013–2020 Eaton, Raleigh, NC, USA. All rights reserved. No part of this document may be reproduced in any way without the express written approval of Eaton.
  • Page 3 5.10 Third Party Intellectual Property Rights. The Firmware may contain components transfer the Firmware directly to a third party only in connection with the sale of the Eaton (including open source software components) that are owned by third parties (“Third Party product in which it is installed.
  • Page 5 4 4 U U P P S S S S y y s s t t e e m m I I n n s s t t a a l l l l a a t t i i o o n n ....................................................2 2 5 5 Eaton 93E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164000301—Rev 04...
  • Page 6 7.2.2 System Events........................... 68 7.2.3 Using the LCD and Pushbuttons ......................68 7.2.4 Using the Menu..........................69 7.2.5 Mimic Screen ............................ 70 7.2.6 Display Menu Operation........................71 7.2.7 System Controls..........................74 Eaton 93E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164000301—Rev 04...
  • Page 7 9.1 Important Safety Instructions ........................93 9.2 Performing Preventive Maintenance ......................93 9.2.1 DAILY Maintenance ..........................94 9.2.2 MONTHLY Maintenance ........................94 9.2.3 PERIODIC Maintenance ........................95 9.2.4 ANNUAL Maintenance......................... 95 Eaton 93E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164000301—Rev 04...
  • Page 8 1 1 1 1 W W a a r r r r a a n n t t y y ........................................................... . 1 1 0 0 1 1 viii Eaton 93E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164000301—Rev 04...
  • Page 9 UPS System Oneline – Internal Battery and External Battery Capable ............63 Figure 37. UPS System Oneline – Internal and External Batteries................64 Figure 38. UPS Controls and Indicators ......................65 Figure 39. UPS Breakers ..........................66 Eaton 93E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164000301—Rev 04...
  • Page 10: Table Of Contents

    Typical System Control Screen ....................... 74 Figure 45. REPO Operation .......................... 81 Figure 46. Optional Mini-Slot Cards ........................ 90 Figure 47. XCP Communication Ports ......................91 Figure 48. Air Filter Location ......................... 95 Eaton 93E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164000301—Rev 04...
  • Page 11 Table 4. UPS Cabinet Clearances ......................... 13 Table 5. Input/Output Ratings and External Wiring Requirements for the Eaton 93E–20, 93E–30/20, and 93E–30/ 30 .............................. 18 Table 6. UPS External Power Cable Terminations for the Eaton 93E–20, 93E–30/20, and 93E–30/30......19 Table 7.
  • Page 12 List of Tables Eaton 93E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164000301—Rev 04...
  • Page 13 AC power to protect the customer's load from power failures. The Eaton 93E 20–30 kVA online power protection system is used to prevent loss of valuable electronic information, minimize equipment downtime, and minimize the adverse effect on production equipment due to unexpected power problems.
  • Page 14 The 93E–30/20 and 93E–30/30 UPS battery systems use internal batteries with External Battery Cabinet (EBC) capability. Up to two Eaton 93E External Battery Cabinets (EBCs) can be added to UPS system. The EBCs are connected in parallel with the internal batteries to provide extended run time.
  • Page 15 1 1 . . 2 2 . . 1 1 E E x x t t e e r r n n a a l l B B a a t t t t e e r r y y C C a a b b i i n n e e t t C C a a p p a a b b i i l l i i t t y y EBC capability provides the ability to add Eaton 93E EBCs to the UPS system in addition to the internal batteries.
  • Page 16 The Eaton 93E–20 is also upgradable to full EBC capability with the addition of a 93E–20 to 93E–30/20 field upgrade kit converting the Eaton 93E–20 to a Eaton 93E–30/20 or to an Eaton 93E–30/30 with a 93E–20 to 93E30/30 field upgrade kit.
  • Page 17 (WEEE) in the trash. For proper disposal, contact your local recycling/reuse or hazardous waste center. recycling/reuse or hazardous waste center. recycling/reuse or hazardous waste center. recycling/reuse or hazardous waste center. Eaton 93E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164000301—Rev 04...
  • Page 18 Installation instructions, including site preparation, planning for installation, wiring and safety information, and detailed illustrations of cabinets with dimensional and connection point drawings Refer to the Eaton 93E Integrated Accessory Cabinet-Tie and Bypass Installation and Operation Manual for the following additional information: •...
  • Page 19 E E q q u u i i p p m m e e n n t t R R e e g g i i s s t t r r a a t t i i o o n n Please visit www.eaton.com/pq/register to register your new Eaton UPS / Eaton UPS Accessory. Model Number: Serial Number: Eaton 93E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164000301—Rev 04...
  • Page 20 Introduction Eaton 93E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164000301—Rev 04...
  • Page 21 ELECTRIC ENERGY HAZARD. Do not attempt to alter any UPS or battery wiring or connectors. Attempting to alter wiring can cause injury. • Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes. It may be toxic. Eaton 93E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164000301—Rev 04...
  • Page 22 Ne pas fumer près des accumulateurs. Ne pas produire de flamme ou d’étincelle dans la zone de l’accumulateur. Dissiper l'électricité statique de votre corps en touchant une surface reliée à la terre avant de toucher les accumulateurs. Eaton 93E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164000301—Rev 04...
  • Page 23 Battery Cabinet. NOTE 2 Startup and operational checks for parallel systems or installations with accessory cabinets must be performed by an authorized Eaton Customer Service Engineer, or the warranty terms specified on product's resources page become void. See Chapter 11 Warranty for details.
  • Page 24 The UPS equipment operating environment must meet the weight requirements shown in Table 3 and the size requirements shown in Figure 2 through Figure 5. Dimensions are in millimeters (inches). Eaton 93E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164000301—Rev 04...
  • Page 25 Clearances must comply with all applicable national and local codes. Flexible conduit may be used to adjust between required operation and service clearances. From Right Side of Cabinet None Required None Required From Left Side of Cabinet Eaton 93E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164000301—Rev 04...
  • Page 26 UPS Installation Plan and Unpacking Figure 2. UPS Cabinet Dimensions (Front and Right Side Views) Back Front Right Side Dimensions are in millimeters [inches] Eaton 93E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164000301—Rev 04...
  • Page 27 UPS Installation Plan and Unpacking Figure 3. UPS Cabinet Dimensions (Top and Bottom Views) Front Top View Front Bottom View Dimensions are in millimeters [inches] Eaton 93E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164000301—Rev 04...
  • Page 28 With Batteries (93E–30/20 and 93E–30/30 477 [17.60] 259 [10.20] 399 [15.71] 476 (1049) – Installed – 6 strings) Without Batteries 657 [25.87] 249 [9.80] 399 [15.71] 261 (575) – Shipping Eaton 93E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164000301—Rev 04...
  • Page 29 DO NOT use a single feeder breaker to supply both the UPS and the maintenance bypass. • Phase rotation must be clockwise starting with phase A (rotation A, B, C). Eaton 93E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164000301—Rev 04...
  • Page 30 The number of neutral conductors listed are for single size neutral wiring. A 1.5x sized neutral can be supported by this product. Two terminal landings are provided to accommodate extra neutral wiring. Table 5. Input/Output Ratings and External Wiring Requirements for the Eaton 93E–20, 93E–30/20, and 93E–30/30 Rating 50/60 Hz Units...
  • Page 31 UPS Installation Plan and Unpacking Table 5. Input/Output Ratings and External Wiring Requirements for the Eaton 93E–20, 93E–30/20, and 93E–30/30 (Continued) Number per Phase (each) Amps 56/52 83/79 AC Output to Critical Load (Five Wire) Full Load Current (3) Phases, (1) Neutral, (1) Ground...
  • Page 32 UPS Installation Plan and Unpacking Table 6. UPS External Power Cable Terminations for the Eaton 93E–20, 93E–30/20, and 93E–30/30 (Continued) Tightening Number and Size of Screw Size and Torque Nm (lb Pressure Termination Type Terminal Function Terminal Function AWG or kcmil...
  • Page 33 Do not directly connect relay contacts to the mains related circuits. Reinforced insulation to the mains is required. Read and understand the following notes while planning and performing the installation: Eaton 93E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164000301—Rev 04...
  • Page 34 UPS Cabinet or external Battery Cabinet without batteries, only the following types are recommended. Use of any other battery type inside Eaton cabinets will void the product warranty. When replacing batteries use the same manufacturer and part number originally supplied with the unit to ensure correct harness fit and terminal landing.
  • Page 35 Carefully inspect the outer packaging for evidence of damage during transit. CAUTION Do not install a damaged cabinet. Report any damage to the carrier and contact an Eaton service representative immediately. NOTE For the following step, verify that the forklift or pallet jack is rated to handle the weight...
  • Page 36 While waiting for installation, protect the unpacked cabinet from moisture, dust, and other harmful contaminants. Failure to store and protect the UPS properly may void your warranty. Figure 6. UPS Cabinet as Shipped on Pallet (wood container removed) Eaton 93E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164000301—Rev 04...
  • Page 37 Attach the ramp extension to the front of the ramp by inserting the tabs on the extension into the slots at the bottom of the ramp. If the leveling feet are not fully retracted, turn the leveling feet until they are retracted. Eaton 93E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164000301—Rev 04...
  • Page 38 Roll the cabinet to the final installation location. If installing the cabinet permanently, retain the shipping brackets and hardware; otherwise, recycle the pallet, ramp, and shipping brackets in a responsible manner. Eaton 93E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164000301—Rev 04...
  • Page 39 Figure 8. Attaching the Ramp to the Pallet UPS Cabinet Ramp Bracket and M10 bolt (2 places) Metal Tab (2 places) Pallet Ramp (top panel from wood container) Ramp Extension Eaton 93E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164000301—Rev 04...
  • Page 40 UPS System Installation Figure 9. Removing the Rear Shipping Bracket Rear View of UPS Shipping Bracket Bolts Pallet Shipping Bracket Bolts Rear Shipping Bracket Eaton 93E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164000301—Rev 04...
  • Page 41 Using the hardware provided, install the terminal cover base to the back panel of the UPS using the existing cabinet screw holes (see Figure 12). Proceed to paragraph 4.4 External Battery Cabinet Installation. Eaton 93E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164000301—Rev 04...
  • Page 42 NOTE Do not install the Power Terminal Cover Left and/or Right Side covers if wiring adjacent ancillary cabinets (such as an EBC or IAC) using the power terminal base wiring channel. Eaton 93E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164000301—Rev 04...
  • Page 43 I I n n t t e e g g r r a a t t e e d d T T r r a a n n s s f f o o r r m m e e r r C C a a b b i i n n e e t t I I n n s s t t a a l l l l a a t t i i o o n n If installing an ITC, refer to the Eaton 93E Integrated Transformer Cabinet Installation Manual listed in paragraph 1.7 For More Information...
  • Page 44 I I n n t t e e g g r r a a t t e e d d A A c c c c e e s s s s o o r r y y C C a a b b i i n n e e t t - - T T i i e e If installing an IAC-T, refer to the Eaton 93E Integrated Accessory Cabinet-Tie and Bypass Installation and Operation Manual listed in paragraph 1.7 For More Information...
  • Page 45 (such as an EBC or IAC) using the power terminal base wiring channel. 10. Install the power terminal cover right and left sides using the provided hardware. 11. Proceed to paragraph 4.13 Connecting Internal Battery Strings. Eaton 93E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164000301—Rev 04...
  • Page 46 Battery + and – (A, B, C, N) (Optional) AC Input to UPS Rectifier AC Input to UPS Bypass (A, B, C, N) (A, B, C, N) (Optional) Back Eaton 93E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164000301—Rev 04...
  • Page 47 Neutral (N) AC Input to Phase B (L2) AC Input to Phase C (L3) Phase C (L3) UPS Rectifier Phase B (L2) UPS Bypass Neutral (N) Phase A (L1) Eaton 93E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164000301—Rev 04...
  • Page 48 To locate the appropriate terminals and review the wiring and termination requirements, see paragraph 3.2.3 UPS System Interface Wiring Preparation, Table Figure Figure 17, and Figure Eaton 93E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164000301—Rev 04...
  • Page 49 UPS System Installation Figure 16. Interface Terminal Locations Mini-Slot Communication Bays Interface Terminals Top Rear Panel Back Eaton 93E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164000301—Rev 04...
  • Page 50 Input: Programmable UPS alarm, activated by a remote dry contact closure. Building Alarm 2 – Building Alarm 3 + Input: Programmable UPS alarm, activated by a remote dry contact closure. Building Alarm 3 – Eaton 93E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164000301—Rev 04...
  • Page 51 Install the power terminal cover right and left sides using the provided hardware. Close the UPS outside door and secure the latch. 10. Proceed to paragraph 4.13 Connecting Internal Battery Strings. Eaton 93E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164000301—Rev 04...
  • Page 52 UPS System Installation Figure 19. Interface Terminal Cover Interface Terminal Cover Installed Interface Terminal Cover Eaton 93E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164000301—Rev 04...
  • Page 53 Figure 20. Interface Conduit Landing and Wiring Channel Wiring Access Interface Wiring Channel Zip Tie Mounting Clips (4 places) Interface Conduit Landing Area Power Terminal Cover Base Figure 21. Interface Wiring Access Wiring Access Eaton 93E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164000301—Rev 04...
  • Page 54 Reinstall the power terminal cover top using the retained hardware. Install the power terminal cover right and left sides using the provided hardware. Connect the building alarm interface wiring as shown in Table 11 Figure Eaton 93E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164000301—Rev 04...
  • Page 55 Remove the screws securing the top rear panel (see Figure 16). Supporting the panel, tilt the panel away from the cabinet and disconnect the fan connector from the wiring harness. Eaton 93E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164000301—Rev 04...
  • Page 56 4 4 . . 1 1 1 1 . . 4 4 I I n n s s t t a a l l l l i i n n g g M M i i n n i i - - S S l l o o t t I I n n t t e e r r f f a a c c e e W W i i r r i i n n g g a a n n d d C C o o n n n n e e c c t t i i o o n n s s NOTE LAN drop for use with Mini-Slot cards must be provided by the customer. For installation and setup of an Mini-Slot card, contact an Eaton service representative (see paragraph 1.8 Getting Help To install wiring: If not already installed, install the LAN drop.
  • Page 57 UPS System Installation Figure 23. Parallel UPS Control Wiring Eaton 93E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164000301—Rev 04...
  • Page 58 The REPO switch must be a normally-open or normally-closed latching-type switch not tied into any other circuits. NOTE 4 This procedure is intended for installing the Eaton-supplied REPO switch. If installing another manufacturer's switch, use this procedure, and Figure 26...
  • Page 59 Reinstall the top rear panel by tilting into position and securing the panel using the retained hardware. Reinstall the power terminal cover top using the retained hardware. Eaton 93E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164000301—Rev 04...
  • Page 60 Tightening Torque Contact Block (Either Block) Back of UPS Cabinet Wire Size 3 NO Twisted Wires (2) 7 lb in 14-22 AWG (0.8 Nm) 4 NO (0.75 4.0 mm Eaton 93E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164000301—Rev 04...
  • Page 61 30) for each set of batteries on the battery shelf. NOTE The Eaton 93E–20 model has battery strings installed on two shelves. The Eaton 93E– 30/20 and Eaton 93E–30/30 models have battery strings installed on three shelves. Eaton 93E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164000301—Rev 04...
  • Page 62 Reinstall the internal safety shield panel removed in Step Close the outside door and secure the latch. Figure 28. Battery Location Front Bottom Internal Safety Shield Panel (Batteries are located behind safety shield.) Eaton 93E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164000301—Rev 04...
  • Page 63 Battery Strings NOTE The Eaton 93E–20 model has battery strings installed on two shelves. The Eaton 93E–30/20 and Eaton 93E–30/30 models have battery strings installed on three shelves. Eaton 93E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164000301—Rev 04...
  • Page 64 Chapter 11 Warranty for details. This service is offered as part of the sales contract for the UPS. Contact an Eaton service representative in advance (usually a two-week notice is required) to reserve a preferred startup date. 4 4 . . 1 1 5 5 C C o o m m p p l l e e t t i i n n g g t t h h e e I I n n s s t t a a l l l l a a t t i i o o n n C C h h e e c c k k l l i i s s t t The final step in installing the UPS system is completing the following Installation Checklist.
  • Page 65 Accessories are mounted in installed locations and wiring is terminated inside the UPS cabinet. (Optional) o Air conditioning equipment is installed and operating correctly. o The area around the installed UPS system is clean and dust-free. (Eaton recommends that the UPS be installed on a level floor suitable for computer or electronic equipment.) o Adequate workspace exists around the UPS and other cabinets.
  • Page 66 UPS System Installation _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ Eaton 93E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164000301—Rev 04...
  • Page 67 U U P P S S S S y y s s t t e e m m O O v v e e r r v v i i e e w w The Eaton 93E UPS is a continuous-duty, solid-state, transformerless, three-phase, true online system that provides conditioned and uninterruptible AC power to the UPS system's output and critical load.
  • Page 68 5 5 . . 2 2 . . 1 1 M M o o d d e e s s The Eaton 93EUPS supports a critical load in four different modes of operation: • In High-Efficiency (HE) Normal mode, commercial AC power is supplied directly to the critical load through the internal bypass and transfers automatically to Standard Normal mode (double-conversion on demand) if an abnormal condition is detected.
  • Page 69 Some power line filtering and spike protection is provided to the load but no active power conditioning or battery support is available to the output of the system in the Bypass mode of operation. Eaton 93E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164000301—Rev 04...
  • Page 70 In Battery mode, the battery provides emergency DC power that the inverter converts to AC power. Figure 34 shows the path of electrical power through the UPS system when operating in Battery mode. Eaton 93E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164000301—Rev 04...
  • Page 71 Normal mode. Depending on the total load and the duration of the battery discharge, battery current limit alarms may be seen for a short time due to the current required to recharge the battery. Eaton 93E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164000301—Rev 04...
  • Page 72 Understanding UPS Operation Eaton 93E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164000301—Rev 04...
  • Page 73 Single Reverse Transfer UPS with Internal 93E–30/20 Figure 36 208/220 208/220 Battery and External Battery Capable 93E–30/30 Single Reverse Transfer UPS with Internal and 93E–30/20 Figure 37 208/220 208/220 External Batteries 93E–30/30 Eaton 93E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164000301—Rev 04...
  • Page 74 Bypass Switchgear Inverter Static Switch Inverter Switchgear Fuse AC Output to Critical Load L1, L2, L3, N Battery Converter Battery Switchgear Fuses UPM 1 Internal Battery UPS CABINET Eaton 93E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164000301—Rev 04...
  • Page 75 Inverter Switchgear Fuse AC Output to Critical Load L1, L2, L3, N Battery Converter Battery Switchgear Fuses UPM 1 External Battery Input Battery Breaker Internal Battery UPS CABINET Eaton 93E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164000301—Rev 04...
  • Page 76 L3, N Battery Converter Battery Switchgear Fuses UPM 1 External Battery Input Battery Breaker Battery Breaker EXTERNAL BATTERY CABINET UPS CABINET Internal Battery (Not supplied with the UPS) Eaton 93E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164000301—Rev 04...
  • Page 77 The controls and indicators identified and described in this section are used to control and monitor UPS operation. Figure 38 shows the controls and indicators and Figure 39 shows the UPS breakers. Figure 38. UPS Controls and Indicators Control Panel Door Latch Eaton 93E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164000301—Rev 04...
  • Page 78 The following paragraphs describe the UPS control panel, including controls and indicators, and how to monitor UPS operation. The control panel (see Figure 40) is located on the front door of the UPS. Eaton 93E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164000301—Rev 04...
  • Page 79: Figure 40. Ups Control Panel

    The following paragraphs describe using the UPS control panel to monitor the UPS. See paragraph 7.3 Single UPS Operation for use of the operational controls. When the unit powers up, the screen displays the Eaton logo as shown in Figure 40. To advance to the Main Menu and Mimic screen, press any control panel pushbutton once.
  • Page 80 7 7 . . 2 2 . . 3 3 U U s s i i n n g g t t h h e e L L C C D D a a n n d d P P u u s s h h b b u u t t t t o o n n s s The LCD on the control panel provides an operator interface with the UPS system. Figure 41 identifies the display areas discussed in the following sections. Eaton 93E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164000301—Rev 04...
  • Page 81: Figure 41. Parts Of The Lcd

    Controls Setup A The UPS status area automatically scrolls between the Eaton model number, current date and time, active alarms, UPS status, load percent, and battery runtime for the UPS. The top line of display blinks while scrolling when the system needs attention. Some notices and alarms may be accompanied by an audible horn. To silence the horn, press any control panel pushbutton once.
  • Page 82: Figure 42. Main Menu And Mimic Screen

    EATON 9395 UPS (650–825 kVA) Installation and Operation Manual 164201725 Rev 4P Draft 31-Jan-2010 EATON 9395 UPS (650–825 kVA) Installation and Operation Manual 164201725 Rev 4P Draft 31-Jan-2010 Eaton 93E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164000301—Rev 04...
  • Page 83 To return to the System Setup screen, press the ESC pushbutton. About The About screen provides the firmware version numbers installed on the UPS. Use the LEFT or RIGHT arrow pushbuttons to select USER on the Setup menu Eaton 93E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164000301—Rev 04...
  • Page 84 Unit Name screen. Use the LEFT or RIGHT arrow pushbutton to highlight the character to be changed. Use the UP or DOWN arrow pushbutton to make the change. When finished making changes, use the Eaton 93E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164000301—Rev 04...
  • Page 85: Figure 43. Typical Initial Setup Screen

    7.2.7 System Controls for details. Figure 43. Typical Initial Setup Screen Status: Status: Status: Status: Load Load Load Load Off Info Info About About Config Config User User Service Service Eaton 93E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164000301—Rev 04...
  • Page 86: Figure 44. Typical System Control Screen

    Starts the UPS in High Efficiency (HE) Normal mode or transfers the UPS to HE Normal mode from Bypass mode. Bypass Mode Starts the UPS in Normal mode or transfers the UPS to Normal mode from Bypass mode. Eaton 93E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164000301—Rev 04...
  • Page 87 S S i i n n g g l l e e U U P P S S O O p p e e r r a a t t i i o o n n NOTE 1 If an External Battery Cabinet (EBC) is installed, refer to the Eaton 93E External Battery Cabinet Installation Manual listed in paragraph 1.7 For More Information...
  • Page 88 If two EBCs are installed, EBC 1 must be closed to supply DC input to the UPS. EBC 2 may be left open, but battery runtime will be reduced. Eaton 93E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164000301—Rev 04...
  • Page 89 7 7 . . 3 3 . . 5 5 T T r r a a n n s s f f e e r r f f r r o o m m H H E E N N o o r r m m a a l l M M o o d d e e t t o o S S t t a a n n d d a a r r d d N N o o r r m m a a l l M M o o d d e e To transfer the load to Standard Normal mode: Select the CONTROLS symbol on the main menu bar. The System Control screen is displayed. Eaton 93E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164000301—Rev 04...
  • Page 90 Select Battery on the System Control screen. On the Battery System Control screen, select the RESTING CHARGING command, then press the RETURN pushbutton. To turn the battery charger off: Eaton 93E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164000301—Rev 04...
  • Page 91 To restart the UPS after pressing the LOAD OFF pushbutton, follow the procedure in paragraph 7.3.1 Starting the UPS in High-Efficiency Normal Mode (Default Mode) 7.3.2 Starting the UPS in Bypass Mode. Eaton 93E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164000301—Rev 04...
  • Page 92 NOTE The following instructions are for the Eaton-supplied REPO switch. If a customer- supplied REPO switch is used, it may not activate in the same manner; refer to the operating instructions provided with the switch.
  • Page 93: Figure 45. Repo Operation

    The paragraphs in this section provide operating instructions for a UPS system containing multiple UPSs. NOTE 1 If an External Battery Cabinet (EBC) is installed, refer to the Eaton 93E External Battery Cabinet Installation Manual listed in paragraph 1.7 For More Information for EBC battery breaker location.
  • Page 94 11. Observe the UPS control panel displays becoming active, indicating logic power. 12. Verify no alarms are active. 13. Select the CONTROLS symbol on the main menu bar. The System Control screen is displayed. Eaton 93E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164000301—Rev 04...
  • Page 95 On the UPS System Control screen, select the HE: ENABLE DISABLE command, then press the RETURN pushbutton. All of the UPSs transfer to Standard Normal mode. The NORMAL status indicator is illuminated. Eaton 93E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164000301—Rev 04...
  • Page 96 If EBCs are installed, close the battery breakers. On the UPS being restarted, observe the UPS control panel display becoming active, indicating logic power. Verify no alarms are active on the UPS being restarted. Eaton 93E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164000301—Rev 04...
  • Page 97 Select Battery on the System Control screen. On the Battery System Control screen, select the RESTING CHARGING command, then press the RETURN pushbutton. To turn an individual UPS battery charger off: Eaton 93E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164000301—Rev 04...
  • Page 98 If another UPS is to be shut down, proceed to that UPS and repeat Step 1 through Step CAUTION Do not attempt to restart the system after Load Off until the cause of the shutdown has been identified and cleared. Eaton 93E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164000301—Rev 04...
  • Page 99 NOTE The following instructions are for the Eaton-supplied REPO switch. If a customer- supplied REPO switch is used, it may not activate in the same manner; refer to the operating instructions provided with the switch.
  • Page 100 UPS Operating Instructions Eaton 93E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164000301—Rev 04...
  • Page 101 M M i i n n i i - - S S l l o o t t C C a a r r d d s s The Eaton 93E UPS has two standard, factory-installed Mini-Slot communication bays. The UPS is compatible...
  • Page 102: Figure 46. Optional Mini-Slot Cards

    UPS battery voltage level below the low voltage threshold Low Battery warning is active NOTE Each relay connection has a NO and NC contact and an isolated relay Eaton 93E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164000301—Rev 04...
  • Page 103: Figure 47. Xcp Communication Ports

    It’s also powered by CA Technologies, bringing together the best in hardware and software. PredictPulse Service is included at no charge during the first year of Eaton 93E UPS operation (warranty period) along with the required connectivity parts. Beyond that, it may be purchased with Eaton Support Agreements or as a standalone subscription after the initial warranty expires.
  • Page 104 Real-time alarm events for all subscribed devices via the PredictPulse mobile app (Apple and Android). You can track all alarms by device. As critical alarms occur, Eaton will acknowledge them so you know when Eaton has diagnosed the alarm (and pending notification of resolution).
  • Page 105 Each battery string is an energy source in itself. DO NOT ATTEMPT TO ACCESS ANY INTERNAL AREA OF THE BATTERY STRING YOURSELF. VOLTAGES ARE ALWAYS PRESENT IN THE BATTERY STRING. If you suspect that a battery string needs service, contact an Eaton service representative. If the string requires service contact an Eaton service representative.
  • Page 106 Ensure the UPS is in Normal mode (Normal status indicator is illuminated). If an alarm lamp is illuminated or the Normal status indicator is not illuminated, contact an Eaton service representative. 9 9 . . 2 2 . . 2 2 M M O O N N T T H H L L Y Y M M a a i i n n t t e e n n a a n n c c e e...
  • Page 107: Figure 48. Air Filter Location

    9 9 . . 2 2 . . 4 4 A A N N N N U U A A L L M M a a i i n n t t e e n n a a n n c c e e Annual preventive maintenance should be performed only by authorized service personnel familiar with maintenance and servicing of the UPS system. Contact an Eaton service representative for more information about service offerings.
  • Page 108 Phillips and Pozidriv are registered trademarks of Phillips Screw Company. A basic training course, available from Eaton, gives you a competent working knowledge of the UPS system Copyright 2008–2010 Eaton Corporation, Raleigh, NC, USA. All rights reserved. No part of this document may be reproduced in any way without the express written approval of Eaton Corporation.
  • Page 109 Output Current Table Output Voltage Balance < 2% for 100% maximum load imbalance (linear load) Output Voltage Phase Displacement < 2.5° for 100% maximum load imbalance (linear load) Eaton 93E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164000301—Rev 04...
  • Page 110 Runtime 93E–20 20 kVA 12.0 93E–30/20 20 kVA 22.0 93E–30/30 30 kVA 12.0 NOTE Battery times are approximate and vary depending on the load configuration and battery charge. Eaton 93E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164000301—Rev 04...
  • Page 111 138.0 45.6 93E–30/30 30 kVA 93E 30EBC 93E–30/30 30 kVA 93E 30EBC 84.5 NOTE Battery times are approximate and vary depending on the load configuration and battery charge. Eaton 93E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164000301—Rev 04...
  • Page 112 Product Specifications Eaton 93E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164000301—Rev 04...
  • Page 113 C C h h a a p p t t e e r r 1 1 1 1 W W a a r r r r a a n n t t y y For warranty information, please refer to the Resources link on our website, www.eaton.com/93E.
  • Page 114 16400030104 164000301 04...