Eaton 93E 30IAC-D Installation And Operation Manual
Eaton 93E 30IAC-D Installation And Operation Manual

Eaton 93E 30IAC-D Installation And Operation Manual

Integrated accessory cabinet-distribution
Table of Contents

Advertisement

Quick Links

®
Eaton
93E Integrated Accessory Cabinet-Distribution
30IAC-D and 60IAC-D
Installation and Operation Manual

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 93E 30IAC-D and is the answer not in the manual?

Questions and answers

Summary of Contents for Eaton 93E 30IAC-D

  • Page 1 ® Eaton 93E Integrated Accessory Cabinet-Distribution 30IAC-D and 60IAC-D Installation and Operation Manual...
  • Page 3 ® Eaton 93E Integrated Accessory Cabinet-Distribution 30IAC-D and 60IAC-D Installation and Operation Manual...
  • Page 4 National Electrical Code and NEC are registered trademarks of National Fire Protection Association, Inc. All other trademarks are property of their respective companies. ©Copyright 2011–2015 Eaton Corporation, Raleigh, NC, USA. All rights reserved. No part of this document may be reproduced in any way without the express written approval of Eaton Corporation.
  • Page 5: Table Of Contents

    Maintenance Training ..............Eaton 93E Integrated Accessory Cabinet-Distribution (30IAC-D and 60IAC-D) Installation and Operation Manual P-164000072—Rev 2...
  • Page 6 WARRANTY ....................Eaton 93E Integrated Accessory Cabinet-Distribution (30IAC-D and 60IAC-D) Installation and Operation Manual P-164000072—Rev 2...
  • Page 7 Figure 4-18. Subfeed Output Terminal Location– 93E 30IAC-D and 93E 60IAC-D ......
  • Page 8 List of Figures This page intentionally left blank. Eaton 93E Integrated Accessory Cabinet-Distribution (30IAC-D and 60IAC-D) Installation and Operation Manual P-164000072—Rev 2 www.eaton.com/powerquality...
  • Page 9 IAC-D Cabinet Clearances ............. . . Table 3-3. External Power Wiring Requirements for the Eaton 93E 30IAC-D and 60IAC-D..... . 3-10 Table 3-4.
  • Page 10 List of Tables This page intentionally left blank. Eaton 93E Integrated Accessory Cabinet-Distribution (30IAC-D and 60IAC-D) Installation and Operation Manual P-164000072—Rev 2 www.eaton.com/powerquality...
  • Page 11: Introduction

    The distribution options are custom configurable, enabling adaptation and expansion without costly electrical rework. Two models are available, the 93E 30IAC-D and 93E 60IAC-D. The IAC-D is housed in a single free-standing cabinet with safety shields behind the front door for hazardous voltage protection.
  • Page 12: Features

    93E 60IAC-D for use with the 93E 60 kVA UPS - Contains one PRL1a 225A 42-pole distribution panel - Up to three JG-Frame 3-pole 250A subfeed breakers Eaton 93E Integrated Accessory Cabinet-Distribution (30IAC-D and 60IAC-D) Installation and Operation Manual P-164000072—Rev 2 www.eaton.com/powerquality...
  • Page 13: Figure 1-3. Eaton 93E 60 Kva Ups And Eaton 93E 60Iac-D

    Introduction IAC-D Figure 1-2. Eaton 93E 30 kVA UPS and Eaton 93E 30IAC-D IAC-D Figure 1-3. Eaton 93E 60 kVA UPS and Eaton 93E 60IAC-D Eaton 93E Integrated Accessory Cabinet-Distribution (30IAC-D and 60IAC-D) Installation and Operation Manual P-164000072—Rev 2 www.eaton.com/powerquality...
  • Page 14: Using This Manual

    This symbol indicates that you should not discard waste electrical or electronic equipment (WEEE) in the trash. For proper disposal, contact your local recycling/reuse or hazardous waste center. Eaton 93E Integrated Accessory Cabinet-Distribution (30IAC-D and 60IAC-D) Installation and Operation Manual P-164000072—Rev 2 www.eaton.com/powerquality...
  • Page 15: For More Information

    UPS, and information about maintenance and responding to system events Communication capabilities of the UPS system Refer to the Eaton 93E Integrated Accessory Cabinet-Tie and Bypass Installation and Operation Manual for the following additional information: Installation instructions, including site preparation, planning for installation, wiring and safety information,...
  • Page 16 Introduction This page intentionally left blank. Eaton 93E Integrated Accessory Cabinet-Distribution (30IAC-D and 60IAC-D) Installation and Operation Manual P-164000072—Rev 2 www.eaton.com/powerquality...
  • Page 17: Safety Warnings

    Failure to anchor the cabinet could lead to injury or death. To reduce this risk, the distribution, tie, and bypass cabinets must be secured to the building floor or to an adjacent 93E system cabinet. Eaton 93E Integrated Accessory Cabinet-Distribution (30IAC-D and 60IAC-D) Installation and Operation Manual P-164000072—Rev 2 www.eaton.com/powerquality...
  • Page 18 Keep surroundings uncluttered, clean, and free from excess moisture. Observe all DANGER, WARNING, and CAUTION notices affixed to the inside and outside of the equipment. Eaton 93E Integrated Accessory Cabinet-Distribution (30IAC-D and 60IAC-D) Installation and Operation Manual P-164000072—Rev 2 www.eaton.com/powerquality...
  • Page 19: Section 1 - Installation

    Section 1 Installation...
  • Page 21: Installation Plan And Unpacking

    Chapter 3 Installation Plan and Unpacking Use the following basic sequence of steps to install the Eaton 93E 30 or 60 Integrated Accessory Cabinet-Distribution (IAC-D): Create an installation plan for the IAC-D (Chapter 3). Prepare your site for the IAC-D (Chapter 3).
  • Page 22: Table 3-1. Iac-D Cabinet Weights

    From Left Side of Cabinet None Required The basic environmental requirements for operation of the IAC-D are: - Recommended Operating Range: 15–25C (59–77F) - Maximum Relative Humidity: 95%, noncondensing Eaton 93E Integrated Accessory Cabinet-Distribution (30IAC-D and 60IAC-D) Installation and Operation Manual P-164000072—Rev 2 www.eaton.com/powerquality...
  • Page 23 Installation Plan and Unpacking Dimensions are in millimeters [inches] Figure 3-1. 93E 30IAC-D Cabinet Dimensions (Front, Right Side, and Rear Views) Eaton 93E Integrated Accessory Cabinet-Distribution (30IAC-D and 60IAC-D) Installation and Operation Manual P-164000072—Rev 2 www.eaton.com/powerquality...
  • Page 24: Figure 3-2. 93E 30Iac-D Dimensions (Top And Bottom Views)

    Installation Plan and Unpacking Dimensions are in millimeters [inches] Figure 3-2. 93E 30IAC-D Dimensions (Top and Bottom Views) Eaton 93E Integrated Accessory Cabinet-Distribution (30IAC-D and 60IAC-D) Installation and Operation Manual P-164000072—Rev 2 www.eaton.com/powerquality...
  • Page 25: Figure 3-3. 93E 30Iac-D Center Of Gravity

    Installation Plan and Unpacking Dimensions are in millimeters [inches] Figure 3-3. 93E 30IAC-D Center of Gravity Eaton 93E Integrated Accessory Cabinet-Distribution (30IAC-D and 60IAC-D) Installation and Operation Manual P-164000072—Rev 2 www.eaton.com/powerquality...
  • Page 26 Installation Plan and Unpacking Dimensions are in millimeters [inches] Figure 3-4. 93E 60IAC-D Cabinet Dimensions (Front, Right Side, and Rear Views) Eaton 93E Integrated Accessory Cabinet-Distribution (30IAC-D and 60IAC-D) Installation and Operation Manual P-164000072—Rev 2 www.eaton.com/powerquality...
  • Page 27: Figure 3-5. 93E 60Iac-D Dimensions (Top And Bottom Views)

    Installation Plan and Unpacking Dimensions are in millimeters [inches] Figure 3-5. 93E 60IAC-D Dimensions (Top and Bottom Views) Eaton 93E Integrated Accessory Cabinet-Distribution (30IAC-D and 60IAC-D) Installation and Operation Manual P-164000072—Rev 2 www.eaton.com/powerquality...
  • Page 28 Installation Plan and Unpacking Dimensions are in millimeters [inches] Figure 3-6. 93E 60IAC-D Center of Gravity Eaton 93E Integrated Accessory Cabinet-Distribution (30IAC-D and 60IAC-D) Installation and Operation Manual P-164000072—Rev 2 www.eaton.com/powerquality...
  • Page 29: Iac-D Power Wiring Preparation

    225A distribution panels use Cutler-Hammer bolt-on type BAB or QBHW breakers for bolt-on panels. Breakers to be provided by the customer. Refer to the appropriate Eaton 93E UPS installation and operation manual listed in paragraph 1.7 for UPS cabinet conduit and terminal specifications and locations.
  • Page 30: Table 3-3. External Power Wiring Requirements For The Eaton 93E 30Iac-D And 60Iac-D

    Table 3-5 for external output power cable terminations. Figure 4-11 and Figure 4-12 show the IAC-D input power terminal locations and detail. Table 3-4. External Input Power Cable Terminations for the Eaton 93E 30IAC-D and 60IAC-D Number and Size of Pressure...
  • Page 31: Table 3-5. External Output Power Cable Terminations For The Eaton 93E 30Iac-D And 60Iac-D

    Installation Plan and Unpacking Table 3-5. External Output Power Cable Terminations for the Eaton 93E 30IAC-D and 60IAC-D Number and Size of Pressure Termination Tightening Torque Type and Size Terminal Function Breaker Rating Terminal Function (AWG or kcmi) Nm (lb in)
  • Page 32: Inspecting And Unpacking The Iac-D

    Carefully inspect the outer packaging for evidence of damage during transit. CAUTION Do not install a damaged cabinet. Report any damage to the carrier and contact an Eaton service representative immediately. NOTE For the following step, verify that the forklift or pallet jack is rated to handle the weight of the cabinet (see Table 3-1).
  • Page 33 Installation Plan and Unpacking 93E 30IAC-D 93E 60IAC-D Figure 3-7. Eaton 93E 30IAC-D and Eaton 93E 60IAC-D as Shipped on a Wooden Pallet Eaton 93E Integrated Accessory Cabinet-Distribution (30IAC-D and 60IAC-D) Installation and Operation Manual P-164000072—Rev 2 www.eaton.com/powerquality 3-13...
  • Page 34 Installation Plan and Unpacking This page intentionally left blank. 3-14 Eaton 93E Integrated Accessory Cabinet-Distribution (30IAC-D and 60IAC-D) Installation and Operation Manual P-164000072—Rev 2 www.eaton.com/powerquality...
  • Page 35: Installation

    (counterclockwise), then swing the door open. If the leveling feet are not fully retracted, turn all four leveling feet until they are retracted into the cabinet. Eaton 93E Integrated Accessory Cabinet-Distribution (30IAC-D and 60IAC-D) Installation and Operation Manual P-164000072—Rev 2 www.eaton.com/powerquality...
  • Page 36 10. If necessary, use a forklift or pallet jack between the supports on the bottom of the pallet to lift the pallet by approximately 3 mm (1/8") and remove the skid (see Figure 4-2). Eaton 93E Integrated Accessory Cabinet-Distribution (30IAC-D and 60IAC-D) Installation and Operation Manual P-164000072—Rev 2 www.eaton.com/powerquality...
  • Page 37 Shipping Bracket Bolts Pallet Rear Shipping Bracket Shipping Bracket Bolts Pallet Extension Plate Mounting Holes (2 places) Figure 4-2. Removing the Rear Shipping Bracket – 93E 30IAC-D Eaton 93E Integrated Accessory Cabinet-Distribution (30IAC-D and 60IAC-D) Installation and Operation Manual P-164000072—Rev 2 www.eaton.com/powerquality...
  • Page 38: Figure 4-3. Installing The Pallet Extension Plate - 93E 30Iac-D

    Installation Pellet Extension Plate (installed for unloading) Figure 4-3. Installing the Pallet Extension Plate – 93E 30IAC-D Eaton 93E Integrated Accessory Cabinet-Distribution (30IAC-D and 60IAC-D) Installation and Operation Manual P-164000072—Rev 2 www.eaton.com/powerquality...
  • Page 39 17 . Secure the cabinet to the floor with customer-supplied hardware. Skip to Step 19. 18. Install cabinet bracket between the IAC-D and the UPS (see Figure 4-4). 19. Skip to paragraph 4.3. Eaton 93E Integrated Accessory Cabinet-Distribution (30IAC-D and 60IAC-D) Installation and Operation Manual P-164000072—Rev 2 www.eaton.com/powerquality...
  • Page 40: Unloading The 60Iac-D

    Install the pallet extension plate onto the rear of the pallet using the retained bolts (see Figure 4-7). Use the mounting holes provided in the pallet (see Figure 4-6). Eaton 93E Integrated Accessory Cabinet-Distribution (30IAC-D and 60IAC-D) Installation and Operation Manual P-164000072—Rev 2 www.eaton.com/powerquality...
  • Page 41 Pallet Extension Plate (installed for shipping) Shipping Bracket Bolts Pallet Shipping Bracket Bolts Front Shipping Bracket Figure 4-5. Removing the Front Shipping Bracket – 93E 60IAC-D Eaton 93E Integrated Accessory Cabinet-Distribution (30IAC-D and 60IAC-D) Installation and Operation Manual P-164000072—Rev 2 www.eaton.com/powerquality...
  • Page 42 Shipping Bracket Bolts Rear Shipping Bracket Skid Bolts (3 places) Pallet Extension Plate Mounting Holes (2 places) Figure 4-6. Removing the Rear Shipping Bracket – 93E 60IAC-D Eaton 93E Integrated Accessory Cabinet-Distribution (30IAC-D and 60IAC-D) Installation and Operation Manual P-164000072—Rev 2 www.eaton.com/powerquality...
  • Page 43: Figure 4-7. Installing The Pallet Extension Plate - 93E 60Iac-D

    Installation Pallet Extension Plate (installed for unloading) Figure 4-7. Installing the Pallet Extension Plate – 93E 60IAC-D Eaton 93E Integrated Accessory Cabinet-Distribution (30IAC-D and 60IAC-D) Installation and Operation Manual P-164000072—Rev 2 www.eaton.com/powerquality...
  • Page 44 17 . Secure the cabinet to the floor with customer-supplied hardware. Skip to Step 19. 18. Install cabinet bracket between the IAC-D and the adjacent UPS (see Figure 4-4). 19. Continue to paragraph 4.3. 4-10 Eaton 93E Integrated Accessory Cabinet-Distribution (30IAC-D and 60IAC-D) Installation and Operation Manual P-164000072—Rev 2 www.eaton.com/powerquality...
  • Page 45: Installing The Power Terminal Cover Base

    NOTE Do not install the Power Terminal Cover Left and/or Right Side covers if wiring adjacent cabinets using the power terminal base wiring channel. Figure 4-8. IAC-D Power Terminal Cover Parts Eaton 93E Integrated Accessory Cabinet-Distribution (30IAC-D and 60IAC-D) Installation and Operation Manual P-164000072—Rev 2 www.eaton.com/powerquality 4-11...
  • Page 46 93E 30IAC-D Rear View NOTE The 93E 30IAC-D is shown. The 93E 60IAC-D terminal cover base installation and conduit landing plate locations are the same. Figure 4-9. IAC-D Power Terminal Cover Base Installation and Rear Conduit Landing Wire Entry Locations 4-12 Eaton 93E Integrated Accessory Cabinet-Distribution (30IAC-D and 60IAC-D) Installation and Operation Manual P-164000072—Rev 2...
  • Page 47: Installing Iac-D External Power Wiring

    Punch or drill holes in the bottom of the power terminal cover base on the UPS cabinet for the AC output conduit. Refer to the applicable Eaton 93E UPS installation and operation manual listed in paragraph 1.7 for UPS cabinet conduit landing location.
  • Page 48 See paragraph 3.2.2, Table 3-3, and Table 3-4 for IAC-D wiring and termination requirements. Refer to the applicable Eaton 93E UPS or 93E Integrated Accessory Cabinet-Tie and Bypass Installation and Operation manual listed in paragraph 1.7 for their respective terminal locations and termination requirements.
  • Page 49: Figure 4-11. Input Power Terminal Locations - 93E 30Iac-D

    27 . Close the inside door and secure with screws. 28. Close the outside door and secure the latch. 29. After the IAC-D is installed and wired, return to the applicable Eaton 93E UPS installation and operation manual listed in paragraph 1.7 to complete the UPS wiring.
  • Page 50: Figure 4-12. Input Power Terminal Detail - 93E 30Iac-D And 93E 60Iac-D

    Ground Terminals Phase A AC Input Phase B to IAC-D Phase C Figure 4-12. Input Power Terminal Detail – 93E 30IAC-D and 93E 60IAC-D 4-16 Eaton 93E Integrated Accessory Cabinet-Distribution (30IAC-D and 60IAC-D) Installation and Operation Manual P-164000072—Rev 2 www.eaton.com/powerquality...
  • Page 51: Figure 4-13. Input Power Terminal Locations - 93E 60Iac-D

    (See Figure 4-12 for detail.) AC Input to IAC-D (A, B, C) (See Figure 4-12 for detail.) Figure 4-13. Input Power Terminal Locations – 93E 60IAC-D Eaton 93E Integrated Accessory Cabinet-Distribution (30IAC-D and 60IAC-D) Installation and Operation Manual P-164000072—Rev 2 www.eaton.com/powerquality 4-17...
  • Page 52: Figure 4-14. Iac-D Power Terminal Cover Installation

    Do not install the Power Terminal Cover Left and/or Right Side covers if wiring adjacent cabinets using the power terminal base wiring channel. Figure 4-14. IAC-D Power Terminal Cover Installation 4-18 Eaton 93E Integrated Accessory Cabinet-Distribution (30IAC-D and 60IAC-D) Installation and Operation Manual P-164000072—Rev 2 www.eaton.com/powerquality...
  • Page 53 93E 30 kVA UPS 93E 30IAC-D NOTE 1 The 93E 30IAC-D and 93E 30 kVA UPS are shown. The 93E 60IAC-D and 93E 60 kVA UPS installation is the same. NOTE 2 The UPS and IAC-D are shown adjacent, but other installed accessory cabinets may be adjacent in large systems with multiple cabinets.
  • Page 54 93E 30 kVA UPS 93E 30IAC-D NOTE 1 The 93E 30IAC-D and 93E 30 kVA UPS are shown. The 93E 60IAC-D and 93E 60 kVA UPS installation is the same. NOTE 2 The UPS and IAC-D are shown adjacent, but other installed accessory cabinets may be adjacent in large systems with multiple cabinets.
  • Page 55: Figure 4-17. Output Power Terminal Locations

    Terminals Ground Terminals AC Subfeed Output (A, B, C) (See Figure 4-18 for detail) Subfeed Output Ground Terminals Figure 4-17. Output Power Terminal Locations Eaton 93E Integrated Accessory Cabinet-Distribution (30IAC-D and 60IAC-D) Installation and Operation Manual P-164000072—Rev 2 www.eaton.com/powerquality 4-21...
  • Page 56: Initial Startup

    W-1 become void. This service is offered as part of the sales contract for the UPS. Contact an Eaton service representative in advance (usually a two-week notice is required) to reserve a preferred startup date.
  • Page 57 A 120 Vac service outlet is located within 7 .5 meters (25 feet) of the IAC-D and UPS equipment. Startup and operational checks are performed by an authorized Eaton Customer Service Engineer. Eaton 93E Integrated Accessory Cabinet-Distribution (30IAC-D and 60IAC-D) Installation and Operation Manual P-164000072—Rev 2 www.eaton.com/powerquality...
  • Page 58 Installation Notes 4-24 Eaton 93E Integrated Accessory Cabinet-Distribution (30IAC-D and 60IAC-D) Installation and Operation Manual P-164000072—Rev 2 www.eaton.com/powerquality...
  • Page 59: Section 2 - Operation

    Section 2 Operation...
  • Page 61: Onelines And Schematics

    NOTE: Neutral and ground connections are not shown in the oneline drawing. See schematics for details. NOTE Callout letters A and B map to Table 3-3. Figure 5-1. 93E 30IAC-D and 93E 60IAC-D Internal Oneline Eaton 93E Integrated Accessory Cabinet-Distribution (30IAC-D and 60IAC-D) Installation and Operation Manual P-164000072—Rev 2 www.eaton.com/powerquality...
  • Page 62: Figure 5-2. 93E 30Iac-D And 93E 60Iac-D Intercabinet Interconnection Online

    Critical Loads 93E IAC-D 93E UPS 93E EBC 1 93E EBC 2 Two Cabinets Maximum Figure 5-2. 93E 30IAC-D and 93E 60IAC-D Intercabinet Interconnection Online Eaton 93E Integrated Accessory Cabinet-Distribution (30IAC-D and 60IAC-D) Installation and Operation Manual P-164000072—Rev 2 www.eaton.com/powerquality...
  • Page 63: Schematics

    Subfeed 3 (3-Phase) LEGEND Subfeed Ground Factory Wiring ° (105 C Insulation) Customer Wiring ° C Insulation) Figure 5-3. 93E 30IAC-D and 93E 60IAC-D Schematic Eaton 93E Integrated Accessory Cabinet-Distribution (30IAC-D and 60IAC-D) Installation and Operation Manual P-164000072—Rev 2 www.eaton.com/powerquality...
  • Page 64 Onelines and Schematics This page intentionally left blank. Eaton 93E Integrated Accessory Cabinet-Distribution (30IAC-D and 60IAC-D) Installation and Operation Manual P-164000072—Rev 2 www.eaton.com/powerquality...
  • Page 65: Figure 6-1. 93E 30Iac-D Breakers

    Subfeed Breakers – Up to three optional subfeed breakers for high current loads Distribution Panel Input Breaker 42-Pole Distribution Panel Subfeed Breakers Figure 6-1. 93E 30IAC-D Breakers Eaton 93E Integrated Accessory Cabinet-Distribution (30IAC-D and 60IAC-D) Installation and Operation Manual P-164000072—Rev 2 www.eaton.com/powerquality...
  • Page 66: Integrated Accessory Cabinet-Distribution Operating Instructions

    Integrated Accessory Cabinet-Distribution Operating Instructions Distribution Panel Input Breaker 42-Pole Distribution Panel Subfeed Breakers Figure 6-2. 93E 60IAC-D Breakers Eaton 93E Integrated Accessory Cabinet-Distribution (30IAC-D and 60IAC-D) Installation and Operation Manual P-164000072—Rev 2 www.eaton.com/powerquality...
  • Page 67: Iac-D Operation

    OPEN Subfeed Breakers (if installed) OPEN Start the UPS. Refer to the applicable Eaton 93E UPS Installation and Operation manual listed in paragraph 1.7 for UPS operating procedures. Close the distribution panel input breaker. Close the distribution panel branch breakers Close the subfeed breakers (if installed).
  • Page 68 Integrated Accessory Cabinet-Distribution Operating Instructions This page intentionally left blank. Eaton 93E Integrated Accessory Cabinet-Distribution (30IAC-D and 60IAC-D) Installation and Operation Manual P-164000072—Rev 2 www.eaton.com/powerquality...
  • Page 69: Maintenance

    Maintenance Training A basic training course, available from Eaton Corporation, gives you a competent working knowledge of the UPS system operation and teaches you how to perform first level corrective maintenance. For more information about training and other services, contact the Help Desk (see paragraph 1.8).
  • Page 70 Maintenance This page intentionally left blank. Eaton 93E Integrated Accessory Cabinet-Distribution (30IAC-D and 60IAC-D) Installation and Operation Manual P-164000072—Rev 2 www.eaton.com/powerquality...
  • Page 71 Output Operating Output Voltage 208/120 Vac nominal 60 Hz 5 Hz Output Wiring: 4W + G Operating Output Frequency Range Output Current See Table 3-3 Eaton 93E Integrated Accessory Cabinet-Distribution (30IAC-D and 60IAC-D) Installation and Operation Manual P-164000072—Rev 2 www.eaton.com/powerquality...
  • Page 72 (operating and storage) Acoustical Noise Not applicable Safety Conformance UL1778 4 edition Agency Markings ULus EMC (Class A) FCC Part 15 Class A and 62040-2 c3 Eaton 93E Integrated Accessory Cabinet-Distribution (30IAC-D and 60IAC-D) Installation and Operation Manual P-164000072—Rev 2 www.eaton.com/powerquality...
  • Page 73 For Product installed (and currently located) outside the fifty (50) United States and the District of Columbia, if, in the opinion of Eaton, a Warranted Item is defective, Eaton's sole obligation, at the option of Eaton, will be to refurbish or replace such defective Warranted Item (not including the costs of labor coverage). The defective Warranted Item will be refurbished or replaced onsite at the End-User's location or such other location as determined by Eaton.
  • Page 74 Eaton shall not be responsible for failure to provide service or parts due to causes beyond Eaton's reasonable control. In no case will Eaton's liability under this Warranty exceed the replacement value of the Warranted Items.
  • Page 76 *P-164000072 2* P-164000072 2...

This manual is also suitable for:

93e 60iac-d

Table of Contents