UPS System Installation
4.5

Installing Interface Connections

4.5.1 Installing Building Alarm Connections

To install wiring:
1.
Verify the UPS system is turned off and all power sources are removed. See Chapter 6, "UPS Operating
Instructions", for shutdown instructions.
2.
To locate the appropriate terminals and review the wiring and termination requirements, see
paragraph 3.2.3, Table 4-1, Figure 4-6 and Figure 4-7 .
3.
Interface cables can enter the UPS via right side panel or a knockout in the top of the cabinet, see Figure
4-9.
4.
Connect the building alarm interface wiring as shown in Table 4-1 and Figure 4-8.
6.
If wiring parallel connections, proceed to paragraph 4.5.2; if wiring Mini-Slot connections, proceed to
paragraph 4.5.3;
FRONT MIDDLE
COVER PLATE
FRONT VIEW
93E 15-40 kVA
4-8
Eaton 93E UPS (15-80 kVA, 380/400/415V) Installation and Operation Manual
Mini-Slot Communication Bays
(See Figure 4-7 for detail)
FRONT MIDDLE
COVER PLATE
Interface Terminals
(See Figure 4-7 for detail)

Figure 4-6. Interface Terminal Locations

Mini-Slot Communication Bays
(See Figure 4-7 for detail)
Interface Terminals
(See Figure 4-7 for detail)
FRONT VIEW
93E 60-80 kVA