Flow Sensor Inputs; Specifications - Badger Meter Data Industrial 3050 Series Installation & Operation Manual

Btu monitor
Hide thumbs Also See for Data Industrial 3050 Series:
Table of Contents

Advertisement

FLOW SENSOR INPUTS

Type
Threshold
Pulse-Di
2.5 VDC
Pulse-K Factor
2.5 VDC
Pull-up-K Factor
2.5 VDC
Analog – 4-20mA
Analog – 0-20mA
Analog – 0-1 VDC
Analog – 0-5 VDC
Analog – 0-10 VDC
Rate Units of Measure: GPM; gal/sec; gal/hr; Mgal/day; LPS; LPM; LPH; ft3/Sec; ft3/min; ft3/hr;m3/sec; m3/min; m3/hr; acre-ft/sec; acre-ft/min; acre-ft/hr; bbl/sec; bbl/min; bbl/hr;
and field programmed custom units 0.00 to 999999999
Total Units: gallons; Mgal; liters; ft3; m3; acre-ft; bbl; and field programmed custom units 0.00 to 999999999

SPECIFICATIONS

Voltage
12-24 VDC / VAC
(Limit: 8-35VDC)
(Limit: 8-28VAC)
DC current draw (~280mA)
AC power rating (~5 VA)
Display
16 character by two-line alphanumeric
dot matrix 7.95mm high backlit LCD
Operating Temperature
-20°C to +70°C
Storage Temperature
-30°C to +80°C
Dimensions
Panel Mount:
3.78"W x 3.78"H x 3.23"D
(96mm x 96mm x 63mm)
Wall Mount:
4.80"W x 4.72"H x 3.63"D
(120mm x 120mm x 92mm)
Weight:
panel mount 12 oz
Series
Option - Analog Output, RS485 (BACnet / Modbus), and USB
Option - Mounting
6-11
Signal Limit
Frequency
30VDC
0.4 Hz to
10kHz
30VDC
0.4 Hz to
10kHz
30VDC
0.4 Hz to
10kHz
50mA Fused
50mA Fused
30VDC
30VDC
30VDC
Pulse and Relays
Both pulse and relay are fully functional as either
totalizing, or Set Point outputs.
Pulse Electrical
1 Amp @ 35VDC/ 30VAC
Closed: 0.5Ω @ 1 AMP Open: >10
Relay Electrical
Resistive load: 5Amp@120VAC/30VDC
Inductive load: 1Amp@120VAC/30VDC
Pulse/Unit Volume (Totalizer)
Driving Source: flow total; Btu total
Units: any predefined or custom unit
Rate: 1 Pulse per 1.0000000 to 99999999 units
Contact Time: 1 to 9999 mS
Set Point (Alarm)
Driving Source: flow rate; Btu rate;
temperature 1; temperature 2, delta T
Units: Any predefined or custom unit
Set Point : 1.0000000 to 999999999
Delay to Set: 1 to 9999 Seconds
Release Point: 1.0000000 to 999999999
Delay to Release: 1 to 9999 seconds
BTU
No Option
Analog Output, RS485 with BACnet and Modbus, and USB
Panel Mount
Wall Mount
Figure 21: Series 3050 Ordering Matrix
Pull-up
Impedance
1K to12VDC
1K to12VDC
100 Ω
100 Ω
100 Ω
100 Ω
100 Ω
Optional Analog Output
Driving Source: flow rate; PID control
Range: 4-20mA; 0-20mA (isolated current sinking
or sourcing)
Sinking: 30VDC @ 0mA maximum; 3 volts
@20mA minimum
Sourcing: 600 W maximum load
8
USB Communication
Provides complete access to all programming and
operation features.
Requirements:
USB 2.0 A to Mini-B 5-Pin Cable
(Example: SYSONIC model UAM56 GWT/B)
RS-485 Communication
Supports: Modbus and BACnet/MSTP
Accessories
Programming kit
Wall mount kit
Example:
3050
3050
Installation & Operation Manual
Aux. Power
Calibration
12VDC@30mA
K + Offset
12VDC@30mA
Pulse/Gal
12VDC@30mA
Pulse/Gal
12VDC@30mA
Pulse/Gal
12VDC@30mA
Linear
12VDC@30mA
Linear
12VDC@30mA
Linear
12VDC@30mA
Linear
-
x
x
0
1
0
1
Page 29