Installation

Electrical Installation

Power Supply Wiring

The Series 3000 flow monitor requires 12...24V DC/AC to operate . See
AC Volt-Amp requirements .
Always use a fused circuit . Connect the positive of the power supply to the flow monitor terminal marked
(ACL/DC+), and connect the negative of the power supply to the flow monitor terminal marked (ACC/DC-) .
If a Badger Meter Data Industrial plugin power supply (Model A-1028) is being used, connect the black-white wire to the
terminal marked (ACL/DC+) and the black wire to the terminal marked (ACC/DC-) .

Flow Sensor Wiring

The Series 3000 flow sensor inputs are extremely versatile, designed to accept either two-wire or three-wire pulse inputs
(Data Industrial 200 Series, 4000 Series) or Analog inputs . Although different rear panel terminals are used, all parameters are
set with the LCD/keypad interface . There are no internal or external jumpers, switches or potentiometers to move or adjust .
The following pulse input types are accommodated:
Pulse DI: Used for all Badger Meter Data Industrial Flow Sensors . Provides an internal pullup resistor and uses and Offset
values for calibration .
Pulse K-Factor: Accepts non zero-crossing inputs but provides no internal pullup, classical K ( pulses/gallon) values for
calibration .
Pullup K-Factor: Provides an internal pullup resistor and uses classical K (pulses/gallon) values for calibration .
N
OTEE:
All the above pulse input types wire the same as shown in
Software Version 1.2.29" on page 13
Page 6
Earth
3
POWER
LV AC/DC (-)
2
LV AC/DC (+)
1
Figure 4: Power supply wiring
for required input configuration .
DSY-UM-01667-EN-05
"Specifications" on page 24
Ground wire should be heavy gauge and as short as possible.
(+) (-)
(Line) (Com)
or
12 . . . 24V DC
12 . . . 24V AC
Power
Power
Supply
Supply
Figure 5 on page
for DC current draw and
Earth
or
Panel
Ground
7 . See
"Programming Flowchart—
April 2017