SiUS12-928
2.7
Removal of the Compressor
Procedure
Step
1
Remove the terminal
cover.
2
Disconnect the
compressor lead wires.
3
Remove the overload
protector.
4
Remove the 2 nuts.
Removal Procedure
Warning
Be sure to wait 10 minutes or more after turning off all power supplies
before disassembling work.
Procedure
Terminal
cover
U(red)
V(yellow)
Overload
protector
Outdoor Unit – 3MXS24JVJU / 4MXS32GVJU
(R6466)
U : red, V : yellow, W : blue
W(blue)
(R9471)
Disconnect the pipings,
referring to page 177.
(R10440)
Points