SiUS12-928_A
5.4
Freeze-up Protection Control or Heating Peak-cut Control
A5
Remote
Controller
Display
Freeze-up protection control
Method of
Malfunction
Detection
Heating peak-cut control
Freeze-up protection control
Malfunction
Decision
Heating peak-cut control
Conditions
Clogged air filter of the indoor unit
Supposed
Dust accumulation on the indoor heat exchanger
Causes
Short-circuited air
Defective indoor heat exchanger thermistor
Defective indoor unit PCB
Service Diagnosis
During cooling operation, the freeze-up protection control (operation halt) is activated according
to the temperature detected by the indoor heat exchanger thermistor.
During heating operation, the temperature detected by the indoor heat exchanger thermistor is
used for the heating peak-cut control (operation halt, outdoor fan stop, etc.).
During cooling operation, the indoor heat exchanger temperature is below 0°C (32°F).
During heating operation, the temperature detected by the indoor heat exchanger thermistor is
above 65°C (149°F).
Troubleshooting
104