Troubleshooting
5.22 Electrical Box Temperature Rise
L3
Remote
Controller
Display
Outdoor Unit LED
A
Display
Method of
An electrical box temperature rise is detected by checking the radiation fin thermistor with the
Malfunction
compressor off.
Detection
With the compressor off, the radiation fin temperature is above
Malfunction
The error is cleared when the temperature drops below
Decision
To cool the electrical components, the outdoor fan starts when the radiation fin temperature
Conditions
18 class
24/32 class
Defective outdoor unit fan
Supposed
Short circuit
Causes
Defective fin thermistor
Disconnection of connector
Defective outdoor unit PCB
135
1
2
3
4
rises above
and stops when it drops below
80°C (176°F)
100°C (212°F)
.
.
70°C (158°F)
75°C (167°F)
70°C (158°F)
85°C (185°F)
SiUS12-928_A
.
Service Diagnosis