Signal Transmission Error (On Outdoor Unit Pcb) (24/32 Class); Signal Transmission Error (On Outdoor Unit Pcb) (24/32 Class)147 - Daikin SUPER MULTI NX G Series Service Manual

Table of Contents

Advertisement

Troubleshooting
5.27 Signal Transmission Error (on Outdoor Unit PCB)
(24/32 Class)
U7
Remote
Controller
Display
Outdoor Unit LED
A
Display
Method of
Communication error between microcomputer mounted on the main PCB and PM1.
Malfunction
Detection
 The abnormality is determined when the data sent from the PM1 can not be received for 9
Malfunction
Decision
 The error counter is reset when the data from the PM1 can be successfully received.
Conditions
 Defective outdoor unit PCB
Supposed
Causes
Troubleshooting
147
1
2
3
4
seconds.
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Turn off the power and turn it on
again.
Error again?
NO
YES
SiUS12-928_A
Replace the outdoor unit
PCB.
The cause can be an
external factor other than
the malfunction.
Observe the operating
condition in long term.
(R7185)
Service Diagnosis

Advertisement