Troubleshooting
5.16 Discharge Pipe Temperature Control
F3
Remote
Controller
Display
Outdoor Unit LED
A
5
Display
Method of
Detected by the discharge pipe thermistor
Malfunction
Detection
If the temperature detected by the discharge pipe thermistor rises above
Malfunction
Decision
The error is cleared when the discharge pipe temperature is dropped below
Conditions
If the error repeats 6 times, the system is shut down.
Reset condition: Continuous run for about 60 minutes without any other error
Refrigerant shortage
Supposed
Defective four-way valve
Causes
Defective discharge pipe thermistor
Defective outdoor unit PCB
Water mixed in refrigerant
Defective electronic expansion valve
Defective stop valve
Troubleshooting
Check No.04
Refer to P.150
Check No.06
Refer to P.152
Check No.11
Refer to P.155
123
1
4
2
1
3
4
4
1
stops.
120°C (248°F)
107°C (225°F)
(Defective outdoor heat exchanger thermistor or outdoor temperature thermistor)
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Check No. 06
Check the thermistors.
Functioning
Check No. 04
Check the electronic
expansion valve.
Functioning
Check No. 11
Check the refrigerant
line.
Functioning
Malfunctioning
Discharge pipe thermistor
Outdoor heat exchanger thermistor
Outdoor temperature thermistor
Malfunctioning
Malfunctioning
Refrigerant shortage
Four way valve
Water mixed
Stop valve
SiUS12-928_A
, the compressor
.
Replace the
defective
thermistor.
Replace the electronic
expansion valve or the coil.
Refer to the refrigerant line
check procedure.
Replace the outdoor unit
PCB.
(R7141)
Service Diagnosis