Daikin SUPER MULTI NX G Series Service Manual page 131

Table of Contents

Advertisement

SiUS12-928_A
Troubleshooting
Check No.05
Refer to P.151
Check No.06
Refer to P.152
Check No.11
Refer to P.155
Service Diagnosis
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Four way valve coil
disconnected (loose)?
NO
Harness out of connector?
NO
Check the continuity of the four way
valve coil and harness.
Disconnect the harness from the
connector.
Resistance
between harnesses about
1000 ~ 2000 Ω?
YES
Check No. 05
Check the four way valve
switching output.
OK
Any thermistor
disconnected?
NO
Check No. 06
Check the thermistors.
OK
Check No. 11
Check the refrigerant
line.
OK
YES
YES
NO
NG
YES
NG
NG
Water mixed
Stop valve
Troubleshooting
Correct it.
Reconnect it.
Replace the four way valve
coil.
Replace the outdoor unit
PCB.
Reconnect them in position.
Replace a defective
thermistor.
Refer to the refrigerant line
check procedure.
Replace the four way valve.
(defective or dust-clogged)
(R11931)
122