11.5 Minimum clearances for fi re protection, cleaning and full service
The following minimum clearances from flammable materials and for connections, cleaning and full service must be
complied with.
DANGER Injury
Follow the installation guidelines for plant rooms. The configuration of the flue must comply with technical
fire protection requirements in accordance with the applicable regulations, standards and guidelines.
Minimum clearances between flue pipe (piece connecting to flue) and combustible components
1
1
15.7
in / 400
mm
for an uninsulated exhaust pipe
1
1
3.9
in / 100
mm
for an insulated flue pipe (min. 0.79 in / 2 cm insulation thickness)
1.97
1
in / 50
2
mm
for tested, double-walled flue system
DIN V 18 160-1
2
in accordance with approval/identification of system flue
Flue connection top
min. 30 mm
min. 1.18 in
1075 mm
42.32 in
Fig. 20
BioWIN 2 Touch Exklusiv/Premium/Exklusiv-S/Klassik –
view from top
min. 30 mm
min. 1.18 in
Recommended minimum room height:
BioWIN 2 Touch Premium/Exklusiv:
BioWIN 2 Touch Klassik/Exklusiv-S:
BioWIN 2 Touch Klassik-L/Exklusiv-SL:
Fig. 21
min. 50 mm
min. 1.97 in
55.98 in / 1422 mm
BioWIN 2 Touch Exklusiv-SL/Klassik-L – view from top
25
min. 30 mm
min. 1.18 in
68.9 in / 1750 mm
70.9 in / 1800 mm
72.8 in / 1850 mm