2.6 Minimum service clearances for fire protection, cleaning
and maintenance
The following minimum service clearances from flammable materials and for connections, cleaning and main-
tenance must be complied with.
Attention!
The configuration of the entire system must comply with technical fire protection requirements in
accordance with the applicable regulations, standards and guidelines.
2.6.1

Masonry feed-throughs for the exhaust pipe

Examples of masonry feed-throughs tested by the IBS – Institut für Brandschutztechnik und Sicherheitsfor-
schung (Institute for Fire Protection Technology and Safety Research)
Multi-layer flammable wall
Fig. 5
Tested masonry feed-throughs for exhaust pipe
Multi-layer flammable wall
There must be a gap of 200 mm from flammable
components all round the exhaust pipe.
Fig. 6
Tested masonry feed-throughs for exhaust pipe
Multi-layer flammable wall
15
Non-flammable wall
All dimensions in mm:
1 ........... Concrete fill
2 ........... Lining pipe
3 ........... Cavity fill with non-flammable material
(e.g. rock wool)
4 ........... Non-flammable cover
5 ........... Exhaust pipe insulation 20 mm
techn. data of insulation:
– Mineral wool insulation
– Melting point: > 1000 °C
– Thermal conductivity: < 0.04 W/mK
– Minimum thickness: 20 mm
6 ........... Multi-layer flammable wall
7 ........... Flue