How To Take Detector Zones Out Of Test - EMS FirePoint 5000 Operating Manual

Hide thumbs Also See for FirePoint 5000:
Table of Contents

Advertisement

EMS 5000 FIREPOINT

12. How To Take Detector Zones Out Of Test

To take zones out of test and back into original state i.e. all on the 5000 FirePoint, insert
the key into the Panels Control Key switch, located at the right of the Panel. Turn the
key to the "ON" Position.
Step
No
1
With the key in the "ON" position, the screen
will display:
2
Press the "0" key and the screen will now
display:
3
Press
displays:
4
Press the "YES" key and the screen will now
display:
5
6
Press the "YES" key and the screen will now
display:
7
Press the "∇" key once and the screen will now
display:
8
Press the "YES" key twice and the screen will
display: (This puts the status back to ACTIVE)
9
Press the "∆" key once and the screen will now
display:
10
Press the "YES" key and the screen will now
display:
Action
the
"∇"
Press the "∇" key until the screen displays:
key
until
the
ENGINEERS OPERATING GUIDE, ISSUE 3.0 – 16/08/10
25
Screen Display
Panel in Access
Date
|***Options ****
> Passwords
| Time and Date
Yes =Select
| Logging
screen
>Fire System Opts <
| Remote Access
Yes= Select
|** Fire system **
> Dev. Disable /Test<
| Net. Disable /Test |
Yes= Select
| Net. Disable /Test
>Det Zone. Dis /Test <
| Brigade Isolate
Yes= Select
| ** Zone Status **
> Zone is: 01
| Status
: Test
Yes= Select
| Zone is
> Status
: Test
| ^^^^^^^^^^^^^^^^|
Yes= Select
| Zone is
> Status
: ACTIVE<
| ^^^^^^^^^^^^^^^^|
Yes= Select
| ** Zone Status **
> Zone is: 01
| Status
: ACTIVE |
Yes= Select
| ** Zone Status **
> Zone is: 02
| Status
: Test
Yes= Select
Time
|
<
|
Time
|
|
Time
|
Time
|
|
Time
|
<
|
Time
: 01
|
<
Time
: 01
|
Time
|
<
Time
|
<
|
Time