EMS 5000 FIREPOINT
11
12
13
14
15
16
This needs to be repeated until all the Detector Zones are in test, then
continue to step 18
17
18
The devices are now ready to be activated, this includes smoking
detectors and triggering call points. When a device is activated the 5000
FirePoint will go into fire, the display will show TEST ALARM and display
the device number and text description. The Sounders/Relays will not
activate.
NOTE: When smoking detectors their LEDs stay on for 20 minutes.
NOTE: For multi panel installations all zones on ALL panels must be put
into test before testing is started.
Press the "∇" key and the screen will now
display: (Make note of the status the zones is in
e.g. ACTIVE, the status will need to be changed
back Later)
Press the "YES" key twice and the screen will
now display: (notice as the "YES" key is pressed
the status changes)
Press the "∆" key until the screen displays:
Press the "YES" key and the screen will now
display:
Press the "∇" key until the screen displays:
Press the "YES" key and the screen
will now display: (notice as the "YES"
key is pressed the status changes)
Press the "NO" key three times and the screen
will now display:
Turn
the
control
position. The screen will now display:
key
to
the
"OFF"
ENGINEERS OPERATING GUIDE, ISSUE 3.0 – 16/08/10
24
| Zone is
: 01
|
> Status
: ACTIVE <
|^^^^^^^^^^^^^^^^ |
Yes= Select
Time
| Zone is
: 01
|
> Status
: Test
<
|^^^^^^^^^^^^^^^^|
Yes= Select
Time
| ** Zone Status **
|
> Zone is: 01
<
| Status
: Test
|
Yes= Select
Time
| ** Zone Status **
|
> Zone is: 02
<
| Status
: ACTIVE |
Yes= Select
Time
| Zone is
: 02
|
> Status
: ACTIVE <
|^^^^^^^^^^^^^^^^ |
Yes= Select
Time
| Zone is
: 02
|
> Status
: Test
<
|^^^^^^^^^^^^^^^^ |
Yes= Select
Time
Panel in Access
Date
Time
Status Normal
Date
Time