How To Re-Instate Devices From Disablement - EMS FirePoint 5000 Operating Manual

Hide thumbs Also See for FirePoint 5000:
Table of Contents

Advertisement

EMS 5000 FIREPOINT

5. How To Re-instate Devices From Disablement

To reactivate a device on the 5000 FirePoint, insert the key into the Panels Control Key
switch, located at the right of the panel. Turn the key to the "ON" position.
Step
No
1
2
3
4
5
6
7
8
9
10
11
Note: The "DETECTOR/ZONE DISABLED" LED on the 5000 FirePoint Panel
will clear and the Disable beep will stop.
Action
With the key in the "ON" position, the screen
will display:
Press the "0" key and the screen will now
display:
Press the "∇" key until the Screen displays:
Press the "YES" key and the screen will now
display:
Press the "YES" key and the screen will now
display:
Press the "0" key and the screen will now
display:
Enter the device number that you want to Re-
enable (e.g. 125) then press the "YES" key and
the Screen will now display:
Press the "∇" key once and the screen will
display:
Press the "YES" key twice and the screen will
now display:
Press the "NO" key three times and the screen
will now display:
Return the Control key to the "OFF" position
and the screen will now display:
ENGINEERS OPERATING GUIDE, ISSUE 3.0 – 16/08/10
11
Screen Display
Panel in Access
Date
Time
|***Options ****
|
>Passwords
<
|Time and Date
|
Yes =Select
Time
|
Logging
|
>Fire System Opts <
|Remote Access
|
Yes = select
Time
|** Fire system **
|
>Dev. Disable/Test <
| Net. Disable/Test
|
Yes= Select
Time
| ** Device Status * |
>Number is: 001
<
|Status
is: ACTIVE |
Yes= Select
Time
Enter Device
(Number 1-256)
Number > _
Yes = Finish
Time
| ** Device Status * |
>Number is: 125
<
|Status
is: DISABLE|
Yes= Select
Time
|Number is: 125
|
>Status is: DISABLE<
| Zone is
: 01
|
Yes= Select
Time
|Number is: 125
|
>Status is : ACTIVE <
| Zone is
: 01
|
Yes= Select
Time
Panel in Access
Date
Time
Status Normal
Date
Time

Advertisement

Table of Contents
loading

Table of Contents