Enabling/Disabling Zones - EMS FirePoint System 5000 User Manual

Fire alarm
Hide thumbs Also See for FirePoint System 5000:
Table of Contents

Advertisement

EMS SYSTEM 5000
Note: If an event is displayed the Fire System Menu is immediately accessed by turning
the Key into the "ON" Position and pressing the "0" Key.
Then press the "∇" button to highlight ">Status is :Active <", and scroll through the
different status types by pressing the "YES" key until desired option has been found,
then press the "NO" key three times, to return to the main display.
Whilst a device is disabled, the "DETECTOR/ZONE DISABLED" LED Indicator will
illuminate. When the devices are enabled the LED Indicator will extinguish, unless any
detection zones are disabled.

9.4 Enabling/Disabling Zones:

To Enable/Disable a zone from the main screen:
With the control key switch in the "ON" position, press the "0" key, then scroll down, by
pressing the "∇" button to last option, ">Fire System Options<".
Press the "YES" key. Now, press the "∇" button until highlighting ">Det Zone Dis/Test<".
Now press the "YES" key again. Now press the "0" key and enter the desired Zone
Number and press the "YES" key.
| ** Zone Status **
> Zone
is :
| Status
: ACTIVE |
Yes
= Select
Press the "∇" button and scroll through the different status types by pressing the "YES"
key until desired option has been found, then press the "YES" Key.
Now press the "NO" key until to return to the main display.
Whilst a zone is disabled, the "DETECTOR/ZONE DISABLED" LED Indicator will light.
When the zones are enabled the LED Indicator will extinguish, unless a Detector is
Disabled.
|
01
<
12:00
| Zone
is : 01
> Status
: DISABLE <
| ^^^^^^^^^^^^^^^^^^
Yes
= Select
USER MANUAL, ISSUE 2.4 – 19/11/09
|
|
12:00