Reference Manual
00809-0100-4408
Holes
Antenna
Figure 3-9: Still Pipe Requirements
A. Maximum 0.2 in. (5 mm)
B. Maximum 1 in. (25 mm)
C. Minimum 6 in. (150 mm)
D. Maximum 1°
E. Level = 100%
F. Level = 0%
(1)
A larger gap is inevitable for the 4-in. cone antenna in pipes with a diameter larger than 4 in.
Rosemount 5408 and 5408:SIS Level Transmitters
The inner surface must be smooth and clear of any rough edges. (Smooth
pipe joints are acceptable, but may reduce accuracy.)
The end of the pipe must extend beyond the zero level.
Maximum hole diameter is 1 in. (25 mm).
Minimum distance between holes is 6 in. (150 mm).
Holes should be drilled on one side only and deburred.
Drill one hole above maximum product surface.
All cone/process seal antenna sizes can be used for still pipe/chamber
installations.
The gap between the cone antenna and the still pipe should be maximum
0.2 in. (5 mm)
(1)
. Larger gaps may result in inaccuracies. If required, order a
larger antenna and cut on location.
Mechanical installation
March 2023
25