Reference Manual
00809-0100-4408
Cause
The device is in simulation or test mode and is not reporting actual information.
Recommended actions
Related information
Use the simulation mode
Restart the device
7.2.11
Electronics temperature out of limits
Category
LCD display
message
Cause
The temperature of the electronics board has exceeded the transmitter's operating range.
Recommended actions
Related information
Ambient temperature limits
7.2.12
Supply voltage low
Category
LCD display
message
Cause
The supply voltage is low and may affect device operation.
Recommended actions
Related information
Power supply
7.2.13
Low signal quality
Category
LCD display
message
Rosemount 5408 and 5408:SIS Level Transmitters
1. If this behavior is not desired, stop simulation or test mode.
2. If the condition persists, restart the device.
Out of Specification
TEMP
LIMITS
1. Verify ambient temperature is within the operating range.
2. Remote mount the transmitter away from the process and environmental
conditions.
Maintenance Required
SUPLY
LOW
1. Check supply voltage is within range.
2. If not needed, disable this alert.
Maintenance Required
LOW
Service and troubleshooting
March 2023
101