40 Lamp Heartland Rave System - 15 minute session
(24) Heartland Rave APR 160 watt lamps in canopy
(16) Heartland Rave 12071 120 watt lamps in bench
(3) 400 watt facial lamps
T-Max™ timer on board (T-Max™ wireless compatible)
Integrated FM stereo system with connections for an MP3/iPod and headphones
(3) 500 cfm exhaust fans
(2) 500 cfm integrated body fan cooling system
26 AMPS initial start up, 23 AMPS running @ 230 VAC (three phase)
30 AMP rated three phase, 220 – 240 volt with ground required (three phase)
(For optimum performance, running voltage should be 230 – 240 VAC.)
(2) .75 KVA Buck/Booster transformer required if outside 220 – 240 VAC (three phase)
44 AMPS initial start up, 38 AMPS running @ 230 VAC (single phase)
50 AMP rated single phase, 220 – 240 volt with ground required (single phase)
(For optimum performance, running voltage should be 230 – 240 VAC.)
(1) 1.0 KVA Buck/Booster transformer required if outside 220 – 240 VAC (single phase)
8' X 9' minimum room size required
1 Ton (12,000 BTU) minimum A/C dedicated into room
Type B seal tight connector supplied located lower back in center of bed. Type B flexible conduit required. *Actual amp
reading will vary depending on voltage – electrician must calculate load/line side amps when using Buck/Booster
transformer to insure proper wire gauge and breaker size. Minimum 8 gauge wire size is recommended for this 30 amp (3
phase) or minimum 6 gauge for 50 amp (single phase) circuit to allow less than 2% voltage drop up to 100 feet. Licensed
electrician must refer to National Electric Codes when determining proper wire gauge and breaker size for each
application. All specifications are subject to change.