AC Output Voltage
Regulation
Total Harmonic Distortion
of Voltage
AC Output Frequency
Peak Efficiency (from
battery)
AC Output Overload
Protection
AC Output Surge Capacity
Nominal Battery Input
Voltage
Min. Battery Voltage for
Inverter Start-up
See chapter "Device
Operation Settings" →
"Settings menu 29" for
details.
Low Battery Warning
Voltage (relative to
nominal AC output
power)
load < 20%
20% ≤ load < 50%
load ≥ 50%
Low Battery Warning
ReturnVoltage (relative to
nominal AC output
power)
load < 20%
20% ≤ load < 50%
load ≥ 50%
Low Battery Voltage
Disconnect (relative to
nominal AC output
power)
load < 20%
20% ≤ load < 50%
load ≥ 50%
High Battery Disconnect
Voltage
High Battery Return
Voltage
DC Voltage Accuracy
DC Offset
www.phocos.com
230 Vac ± 5%
(programmable, 220 ~ 240 Vac)
< 5% for linear load, < 10% for non-linear load at nominal voltage
> 92%
> 93%
100 milliseconds @ ≥ 205% nominal AC output power
5 seconds @ ≥ 150% nominal AC output power
10 seconds @ 110% ~ 150% nominal AC output power
48 Vdc
46.0 Vdc Default
2.0 Vdc. above "Low voltage
disconnect" setting
46.0 Vdc
42.8 Vdc
40.4 Vdc
48.0 Vdc
44.8 Vdc
42.4 Vdc
Programmable, see chapter"Device Operation Settings" → "Settings menu 29" for
details.
44.0 Vdc
40.8 Vdc
38.4 Vdc
66 Vdc
64 Vdc
(programmable, 110 ~ 127 Vac)
50 Hz or 60 Hz (programmable)
> 91%
2x nominal power for 5 seconds
24 Vdc
23.0 Vdc
Default
46.0 Vdc Default
1.0 Vdc.
2.0 Vdc. above "Low
above "Low
voltage disconnect"
voltage
setting
disconnect"
setting
23.0 Vdc
21.4 Vdc
20.2 Vdc
24.0 Vdc
22.4 Vdc
21.2 Vdc
22.0 Vdc
20.4 Vdc
19.2 Vdc
33 Vdc
32 Vdc
± 0.3%V at no load
≦ 100 mV
120 Vac ± 5%
> 92%
> 90%
48 Vdc
24 Vdc
23.0 Vdc
Default
1.0 Vdc.
above "Low
voltage
disconnect"
setting
46.0 Vdc
23.0 Vdc
42.8 Vdc
21.4 Vdc
40.4 Vdc
20.2 Vdc
48.0 Vdc
24.0 Vdc
44.8 Vdc
22.4 Vdc
42.4 Vdc
21.2 Vdc
44.0 Vdc
22.0 Vdc
40.8 Vdc
20.4 Vdc
38.4 Vdc
19.2 Vdc
66 Vdc
33 Vdc
64 Vdc
32 Vdc