Start up
The heat pump will be started by the heat pump controller;
the start up is to be carried out by a competent person.
For this, fi ll in the notice of completion (see page 41) and
fax it to the supplier.
Before the start up, please check the following:
1. The installation and assembly have been carried out in
accordance with the pages 4 to 12?
2. Check the electrical supply for the correct rotation.
3. Check all isolation valves in the heating circuit are
open.
4. Check all isolation valves in the heat source side are
open.
5. Check all heating circuits and brine circuits have been
vented thoroughly.
6. Does the compressor have electrical disconnection
protection?
Maintenance
Clean the device with a damp cloth and a mild cleansing
agent.
Never use scouring, acidic or corrosive agents.
Trouble Shooting
The diagnostic programme within the heat pump
controller will establish errors.
Please fi nd further details referring to diagnosis and trouble
shooting in the heat pump controller instruction manual!