TABLE OF CONTENTS SAFETY REGULATIONS In general, the following recommendations are referred to Page in this instruction manual: Safety Regulations Safety regulations. Important! Please observe! General Please observe advice referring to function and operating method! Scope of Supply Reference to instruction manual of the heat pump Transport controller Installation...
SCOPE OF SUPPLY GENERAL General Scope of Supply • Compact device with fully hermetic compressor and Operative range all relevant safety components for refrigeration circuit monitoring. The heat pump is designed exclusively for the heating of • heating circuit water and domestic hot water. Considering Integrated heat pump- and heating installation-controller.
TRANSPORT Transport with the lift truck To go through narrow passages, you can remove the side panels to reduce the total device width by about 4 cm. To avoid transportation damage, the heat pump should be transported with a lift truck or a pallet truck. Transport the device in packed condition to the fi...
ASSEMBLY HYDRAULICS The hydraulic supply points are on the de- Heat source supply point: vice rear: The heat source installation must be sized in accordance with the prescriptions in the project planning manual. Please note: • Before fi lling the heat source installation, it must be rinsed thoroughly.
HYDRAULIC SCHEMATIC Legend !24) Manometer 25) Heating circulating pump and domestic hot water 1) Heat pump with fl ow and return sensor for the heating system 26) Reversing valve domestic hot water 2) Radiator or fl oor heating system 27) Immersion heater for heating and domestic hot water 3) Vibration-free connection (fl...
ASSEMBLY HYDRAULICS The hydraulic supply points are on device Heating circuit water supply point: rear: The heating system must be fl ushed before connecting the heat pump to prevent contamination inside the heating system affecting the function of the heat pump. Heating circuit water output (fl...
HYDRAULIC SCHEMATIC BRINE/WATER HEAT PUMP PROFESSIONELL, MONOVALENT OPERATION Sanitary hot water storage Buffer storage Heat source instal- lation See hydraulics heat source installation Legend !24) Manometer 25) Heating circulating pump and domestic hot water 1) Heat pump with fl ow and return sensor for the heating system 26) Reversing valve domestic hot water 2) Radiator or fl...
POWER SUPPLY The cables must be led through the cable entry points on the device rear. The strain relief is on the rear The terminal strips are situated in the central control room. Top right, you see the phase guard, shining green when the tension is correct and shining red whenever there is a left-hand rotating fi...
THE OPERATING DEVICE Assembly controller Hang up the ope- rating device in the square spaces, screw it down and put in the cable During the transport, the operating element is stored from the bottom. on the intermediate plate in the device. The appropriate cable is stored top right and is already clipped on the circuit board.
START UP / MAINTENANCE / TROUBLE SHOOTING Start up The heat pump will be started by the heat pump controller; the start up is to be carried out by a competent person. For this, fi ll in the notice of completion (see page 41) and fax it to the supplier.
TECHNICAL DATA SWP 230H H-devices up to maximum 65°C fl ow temperature V.813136 Heat pump type Sole / Wasser Conformity Installation Innen Protection IP24 Power data Heating power/COP B0/W35 acc. to EN255 kW/- 22,8 / 4,0 (12,1 / 4,4) B0/W50 acc.
Page 15
TECHNICAL DATA SWP 330H H-devices up to maximum 65°C fl ow temperature V.813138 Heat pump type Sole / Wasser Conformity Installation Innen Protection IP24 Power data Heating power/COP B0/W35 acc. to EN255 kW/- 32,4 / 4,1 (17,2 / 4,4) 30,2 / 2,8 (16,0 / 3,0) B0/W50 acc.
Page 16
TECHNICAL DATA SWP 410H H-devices up to maximum 65°C fl ow temperature V.813139 Sole / Wasser Heat pump type Conformity Innen Installation IP24 Protection Power data 40,3 / 4,1 (21,4 / 4,4) Heating power/COP B0/W35 acc. to EN255 kW/- 37,5 / 2,8 (19,9 / 3,0) B0/W50 acc.
Page 17
TECHNICAL DATA SWP 500H H-devices up to maximum 65°C fl ow temperature V.813140 Sole / Wasser Heat pump type Conformity Innen Installation IP24 Protection Power data 48,9 / 4,1 (25,9 / 4,4) Heating power/COP B0/W35 acc. to EN255 kW/- 45,4 / 2,8 (24,1 / 3,0) B0/W50 acc.
TECHNICAL DATA SWP 390 M-devices up to maximum 55°C fl ow temperature V.813131a Heat pump type Brine / Water Conformity Installation Indoor Protection IP24 Power data Heating power/COP B0/W35 acc. to EN255 kW/- 38,2 / 4,1 (20,2 / 4,4) B0/W50 acc.
Page 19
TECHNICAL DATA SWP 540 M-devices up to maximum 55°C fl ow temperature V.813133 Brine / Water Heat pump type Conformity Indoor Installation Protection IP24 Power data 54,4 / 4,2 (28,8 / 4,4) Heating power/COP B0/W35 acc. to EN255 kW/- B0/W50 acc.
Page 20
TECHNICAL DATA SWP 670 M-devices up to maximum 55°C fl ow temperature V.813130 Heat pump type Brine / Water Conformity Installation Indoor Protection IP24 Power data Heating power/COP B0/W35 acc. to EN255 kW/- 67,6 / 4,2 (36 / 4,4) B0/W50 acc.
Page 21
TECHNICAL DATA SWP 820 M-devices up to maximum 55°C fl ow temperature V.813135 Heat pump type Brine / Water Conformity Indoor Installation Protection IP24 Power data Heating power/COP B0/W35 acc. to EN255 kW/- 81,9 / 4,2 (43,4 / 4,4) 82,0 / 3,0 (43,5 / 3,1) B0/W50 acc.
EC Declaration of Conformity The undersigned hereby confi rms that the device(s) referred to hereinafter - in the execution put in circulation by us - complies / comply with the harmonized EC-directives, EC-safety standards and product-specifi c EC-standards. In case of a modifi...
NOTICE OF COMPLETION FAX TO □ > AFTER-SALES-SERVICE PARTNER I R E L A N D: +44 28 80 76 08 68 □ > AFTER-SALES-SERVICE PARTNER SCOTL A N D: +44 8700 801020 □ > AFTER-SALES-SERVICE PARTNER E N G L A N D / W A L E S: +44 13 73 82 64 44 __________________________________________________________________________________________________________________ NOTICE OF COMPLETION (NOC) AND REQUEST FOR START-UP BY MANUFACTURER...
Page 41
NOTICE OF COMPLETION CHECK-LIST / NOTICE OF COMPLETION FOR HEAT PUMP INSTALLATION Heat Source Air □ Ducts connected and leak-proof o.k. □ Weather protective grids installed o.k. □ Direction of fan rotation o.k. Heat Source Brine or Water □ Heat source volume rate o.k.
Page 42
- Subject to Technical Modifi cations - 830109aGB/151024...
Page 43
830109aGB/151024 - Subject to Technical Modifi cations -...
Page 44
Alpha-InnoTec GmbH Industriestrasse 3 The future of heatpumps D-95359 Kasendorf Tel.: +49 (0)9228 9906 0 Fax.: +49 (0)9228 9906 29 e-mail: info@alpha-innotec.de www.alpha-innotec.com Certified Quality SCOTLAND ENGLAND / WALES In view of offering the heat pump Renewable Energy Options Ltd.